Plan Review Notes
Plan Review Notes For Permit 03052313
Permit Number 03052313
Review Stop M
Sequence Number 2
Notes
Date Text
2004-07-09 00:00:00DENIED:2ND REQUEST
 COMMENT FROM REVIEW DATED 3-4-04:
 PLANS INDICATE DUCT PENETRATING RATED
 WALLS.FIRE DAMPERS ARE NOT INDICATED
 ON THE PLAN.PER 2001 FBC(M) 607.6,
 FIRE DAMPERS AND ACCESS DOORS ARE TO
 BE INDENTIFIED ON THE PLAN.PROVIDE
 DETAIL FOR FIRE DAMPER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.