2004-03-03 00:00:00 | ******** UNSAT ************* |
| |
| 1)NOTE: PLANS ARE NOW IN FOR PLAN REVIEW |
| THE ELECTRICAL CODE HAS NOW CHANGED TO |
| THE 2002 NEC AS OF JULY 1ST, 2003. |
| PLEASE ADJUST. |
| |
| 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| -ING OF EM/EXT LTS. THIS WAS ON FIRST |
| REVIEW NOTES. |
| |
| 3)NOTE: PLEASE CLARIFY LIGHTING IN MAIN |
| SANCTUARY. NEW OR EXISTING? LS 101 |
| |
| 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| 12 MONTH LOAD IS SHOWN, HOWEVER, HOW |
| CAN THIS BE ACURATE DUE TO ADDITION OF |
| NEW ELECTRICAL AND/ PANEL/LOADS?? |
| LOAD IS ALREADY SHOWN AT 196 A'S |
| PLEASE DO LOAD CALCULATIONS PER ABOVE. |
| |
| 5)NOTE: PLEASE SEE AN EQUIPMENT GROUND- |
| -ING CONDUCTOR IS SHOWN FROM FPL TO |
| MAIN?? PLEASE SEE 250.6, 250.24 THIS IS |
| PARALLELING THE NEUTRAL. |
| PLEASE VERIFY. |
| |
| 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND |
| 61G1-16.004. PLEASE INCLUDE ALL INFORMAT |
| -ION ON TITLE BLOCKS FOR ARCH/ ENG. |
| THIS IS REQUIRED FOR ALL TRADES AND |
| ALL SHEETS WEATHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| PLEASE INCLUDE CERTIFICATE OF AUTHORIZ- |
| ATION REQ'D PER FS 471.023, 481.221 |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |