Plan Review Notes
Plan Review Notes For Permit 03052313
Permit Number 03052313
Review Stop E
Sequence Number 2
Notes
Date Text
2004-03-03 00:00:00******** UNSAT *************
  
 1)NOTE: PLANS ARE NOW IN FOR PLAN REVIEW
 THE ELECTRICAL CODE HAS NOW CHANGED TO
 THE 2002 NEC AS OF JULY 1ST, 2003.
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS. THIS WAS ON FIRST
 REVIEW NOTES.
  
 3)NOTE: PLEASE CLARIFY LIGHTING IN MAIN
 SANCTUARY. NEW OR EXISTING? LS 101
  
 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 12 MONTH LOAD IS SHOWN, HOWEVER, HOW
 CAN THIS BE ACURATE DUE TO ADDITION OF
 NEW ELECTRICAL AND/ PANEL/LOADS??
 LOAD IS ALREADY SHOWN AT 196 A'S
 PLEASE DO LOAD CALCULATIONS PER ABOVE.
  
 5)NOTE: PLEASE SEE AN EQUIPMENT GROUND-
 -ING CONDUCTOR IS SHOWN FROM FPL TO
 MAIN?? PLEASE SEE 250.6, 250.24 THIS IS
 PARALLELING THE NEUTRAL.
 PLEASE VERIFY.
  
 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 61G1-16.004. PLEASE INCLUDE ALL INFORMAT
 -ION ON TITLE BLOCKS FOR ARCH/ ENG.
 THIS IS REQUIRED FOR ALL TRADES AND
 ALL SHEETS WEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
 PLEASE INCLUDE CERTIFICATE OF AUTHORIZ-
 ATION REQ'D PER FS 471.023, 481.221
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  