2004-03-04 00:00:00DENIED:
 PLANS INDICATE DUCTS PENETRATING RATED
 WALLS.FIRE DAMPERS ARE NOT INDICATED
 ON THE PLAN.PER 2001 FBC(M) 607.6,
 SPECIFIC LOCATION OF FIRE DAMPERS AND
 ACCESS DOOR ARE TO BE INDENTIFIED ON
 THE PLAN.
  
 EXEMPTIONS FOR FIRE DAMPERS SHALL COMPLY
 WITH 2001 FBC(M) 607.1.3 #3 ITEMS 1 THR
 OUGH 4.PLEASE CLARIFY.
  