2003-06-25 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03052313 |
| ADD: 2000-6 AE ISAACS AVE |
| CONT: PLAN REVIEW |
| CONTACT PERSON: REGINALDA COX |
| TEL: (561)573-1131 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| NOTE!!!!!! |
| THE REQUIREMENTS OF THE FLORIDA ACCESS- |
| IBILITY ACT MAY NOT REGULATE "CHURCHES" |
| DEPENDING ON THE ACTIVITY OF THE BUILD- |
| ING. SS 553.505 (1995) CH. 97-76 FL |
| LAWS, RELIEVED BUILDINGS USED FOR COMMUN |
| IAL RELIGIOUS OBSERVENCES FROM THE |
| ACCESSIBILITY REQUIREMENTS OF THE ACT. |
| FROM MEMO 8/16/98 ALFRED BRAGG III, |
| ASSISTANT GENERAL COUNSEL |
| |
| IT APPEARS THAT THE DESIGNER IS TRYING |
| TO MEET THE HANDICAPPED REQUIREMENTS, |
| IN THIS REVIEW I WILL INDICATE ANY |
| DISCPENANCIES TO THE FL ACCESSIBILITY |
| CODE WITH (***) BEFORE THE COMMENT EVEN |
| THOUGH IT MAY NOT BE ENFORCED. |
| |
| ACTION : DENIED |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) PLANS INDICATE 2 HR WALLS SEPERATING |
| ASSEMBLY AREAS FROM THE EXIT ACCESS |
| CORRIDORS TABLE 704.2.4 FOR UNSPRINKLER- |
| ED BUILDINGS INDICATE A 1 HR RATING. |
| |
| 3) 1019.7.2 GROUP A OCCUPANCY, EACH DOOR |
| IN A MEANS OF EGRESS FROM AN AREA OF |
| GROUP A OCCUPANCY MAY BE PROVIDED WITH A |
| LATCH OR LOCK ONLY IF IT IS PANIC HARD- |
| WARE OR FIRE EXIT HARDWARE. |
| DOORS MISSING PANIC HARDWARE, 101,102, |
| 105,107,107B, 114 & 114B. |
| |
| 4) STAIRS AT DOOR 114B MISSING LANDING |
| AT DOOR! 1007.4.2 STAIRS SHALL HAVE |
| FLOORS OR LANDINGS AT DOOR OPENINGS. |
| |
| 5)1007.5.2 STAIRWAYS SHALL HAVE HAND- |
| RAILS ON EACH SIDE.EXTERIOR STAIRS AS |
| WELL AS INTERIOR. |
| |
| 6)1015.2 HEIGHT. GUARDRAILS SHALL |
| FORM A VERTICAL PROTECTIVE BARRIER NOT |
| LESS THAN 42" HIGH. |
| |
| 7)1015.3 OPENINGS. OPEN GUARDRAILS |
| SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| REJECT THE PASSAGE OF 2" DIAMETER |
| SPHERE. |
| |
| 8) STAIRWELL SHAFT ENCLOSURE: TABLE |
| 705.1.2. SECOND FLOOR, (BUSINESS OCC) |
| REQUIRES 1 HR.,MISSING AT FIRST FLOOR & |
| DOOR 104, 705.2.3. ALSO SEE 1006.1.3.2 |
| FOR WINDOWS OPENINGS WITHIN 10' OF |
| STAIRWELL SHAFTS, 3/4 HR OPENING PROTECT |
| IVES. |
| |
| *** 9) PLATFORM # 099 |
| 11-4.1.2 VERTICAL ACCESSIBILITY, |
| NOTHING IN THIS CODE SHALL BE CONSTRUED |
| TO RELIEVE THE OWNER OF ANY BUILDING, |
| SSTRUCTURE OR FACILITY FROM THE DUTY TO |
| PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| GRADE LEVEL. |
| |
| *** 10) MANEUVERING CLEARENCES AT DOOR |
| NUMBER 103, 107A, 109,& 114A. |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| |
| *** 11) COMPANION SEATING 11-4.1.6(3) |
| (F)(I) EACH ACCESSIBLE SEATING AREA |
| SHALL HAVE PROVISIONS FOR COMPANION SEAT |
| ING AND SHALL BE LOCATED ON AN ACCESS- |
| IBLE ROUTE THAT ALSO SERVES AS A MEANS |
| OF EMERGENCY EGRESS. |
| |
| 12) HANDRAILS FOR THE HANDICAPPED RAMP: |
| TO COMPLY WITH TABLE 1004, 44" CLEAR BE |
| TWEEN HANDRAILS, ALSO SEE EDGE PROTEC- |
| TION (***) 11-4.8.8 FOR RAMP. NOTE ALSO |
| SEE GUARDRAILS IN NOTE# 7 ABOVE. |
| |
| ****13) 11-4.4.8.4(3) HANDICAPPED RAMPS |
| / LANDINGS, IF RAMPS CHANGE DIRECTION AT |
| LANDINGS, A MIIMUM LANDING SIZE SHALL BE |
| 60"X60"(INSIDE OF THE HANDRAILS/ GUARD- |
| RAIL SYSTEM NOT A OVERALL MEASUREMENT! |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |