Plan Review Notes
Plan Review Notes For Permit 03052313
Permit Number 03052313
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03052313
 ADD: 2000-6 AE ISAACS AVE
 CONT: PLAN REVIEW
 CONTACT PERSON: REGINALDA COX
 TEL: (561)573-1131
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTE!!!!!!
 THE REQUIREMENTS OF THE FLORIDA ACCESS-
 IBILITY ACT MAY NOT REGULATE "CHURCHES"
 DEPENDING ON THE ACTIVITY OF THE BUILD-
 ING. SS 553.505 (1995) CH. 97-76 FL
 LAWS, RELIEVED BUILDINGS USED FOR COMMUN
 IAL RELIGIOUS OBSERVENCES FROM THE
 ACCESSIBILITY REQUIREMENTS OF THE ACT.
 FROM MEMO 8/16/98 ALFRED BRAGG III,
 ASSISTANT GENERAL COUNSEL
  
 IT APPEARS THAT THE DESIGNER IS TRYING
 TO MEET THE HANDICAPPED REQUIREMENTS,
 IN THIS REVIEW I WILL INDICATE ANY
 DISCPENANCIES TO THE FL ACCESSIBILITY
 CODE WITH (***) BEFORE THE COMMENT EVEN
 THOUGH IT MAY NOT BE ENFORCED.
  
 ACTION : DENIED
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS INDICATE 2 HR WALLS SEPERATING
 ASSEMBLY AREAS FROM THE EXIT ACCESS
 CORRIDORS TABLE 704.2.4 FOR UNSPRINKLER-
 ED BUILDINGS INDICATE A 1 HR RATING.
  
 3) 1019.7.2 GROUP A OCCUPANCY, EACH DOOR
 IN A MEANS OF EGRESS FROM AN AREA OF
 GROUP A OCCUPANCY MAY BE PROVIDED WITH A
 LATCH OR LOCK ONLY IF IT IS PANIC HARD-
 WARE OR FIRE EXIT HARDWARE.
 DOORS MISSING PANIC HARDWARE, 101,102,
 105,107,107B, 114 & 114B.
  
 4) STAIRS AT DOOR 114B MISSING LANDING
 AT DOOR! 1007.4.2 STAIRS SHALL HAVE
 FLOORS OR LANDINGS AT DOOR OPENINGS.
  
 5)1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.EXTERIOR STAIRS AS
 WELL AS INTERIOR.
  
 6)1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
  
 7)1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 8) STAIRWELL SHAFT ENCLOSURE: TABLE
 705.1.2. SECOND FLOOR, (BUSINESS OCC)
 REQUIRES 1 HR.,MISSING AT FIRST FLOOR &
 DOOR 104, 705.2.3. ALSO SEE 1006.1.3.2
 FOR WINDOWS OPENINGS WITHIN 10' OF
 STAIRWELL SHAFTS, 3/4 HR OPENING PROTECT
 IVES.
  
 *** 9) PLATFORM # 099
 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
  
 *** 10) MANEUVERING CLEARENCES AT DOOR
 NUMBER 103, 107A, 109,& 114A.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 *** 11) COMPANION SEATING 11-4.1.6(3)
 (F)(I) EACH ACCESSIBLE SEATING AREA
 SHALL HAVE PROVISIONS FOR COMPANION SEAT
 ING AND SHALL BE LOCATED ON AN ACCESS-
 IBLE ROUTE THAT ALSO SERVES AS A MEANS
 OF EMERGENCY EGRESS.
  
 12) HANDRAILS FOR THE HANDICAPPED RAMP:
 TO COMPLY WITH TABLE 1004, 44" CLEAR BE
 TWEEN HANDRAILS, ALSO SEE EDGE PROTEC-
 TION (***) 11-4.8.8 FOR RAMP. NOTE ALSO
 SEE GUARDRAILS IN NOTE# 7 ABOVE.
  
 ****13) 11-4.4.8.4(3) HANDICAPPED RAMPS
 / LANDINGS, IF RAMPS CHANGE DIRECTION AT
 LANDINGS, A MIIMUM LANDING SIZE SHALL BE
 60"X60"(INSIDE OF THE HANDRAILS/ GUARD-
 RAIL SYSTEM NOT A OVERALL MEASUREMENT!
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026