Plan Review Notes
Plan Review Notes For Permit 03052306
Permit Number 03052306
Review Stop M
Sequence Number 1
Notes
Date Text
2003-06-09 00:00:00INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE ENERGY & MANUAL
 J CALCS AS PER 2001 FBC CHAPTER 13 SUB-
 CHAPTER 6.
  
 PROVIDE EQUIPMENT SCHEDULE (NEW OR
 EXISTING).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved