Plan Review Notes
Plan Review Notes For Permit 03052306
Permit Number 03052306
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES AND
 ADD THE FOLLOWING TO THE PLANS FOR CODE
 COMPLIANCE.
  
 1} THE RISER DIAGRAM AND LOAD
 CALCULATION ATTACHED TO THE PLAN IS NOT
 IN THE SCOPE OF WORK DESCRIBED ON THE
 PERMIT APPLICATION OR PART OF THE
 SIGNED AND SEALED PLANS.ALSO THE
 RELOCATED METER IS NOT IN THE
 SCOPE.PLEASE HAVE THE ARCHITECT OF
 RECORD ADD THIS TO THE PLANS AND
 INCLUDE IN THE PROJECT VALUATION,OR
 APPLY FOR A SEPARATE PERMIT FOR THAT
 WORK.
  
 2} PLEASE SUPPLY A PANEL SCHEDULE.
  
 3} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5} SMOKE DETECTORS ARE REQUIRED INSIDE
 AND OUTSIDE BEDROOMS PER 8-1.4.2
 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718