2003-06-11 00:00:00 | ******CORRECTIONS******* |
| |
| 1.)ADDITIONAL PERMITS REQUIRED. |
| |
| 2.)WINDOW B IS REQUIRED TO BE SAFETY |
| GLASS, FBC2405.2.1. |
| |
| 3.)PROVIDE AREA CALCULATIONS ON THE |
| PLAN.IF THE ADDITION AREA IS GREATER |
| THAN 25% OF THE EXISTING, COMPLY WITH |
| FBC 3401.7.1.SHOW EMERGENCY EGRESS |
| FOR BEDROOMS, SMOKE DETECTORS FOR |
| EXISTING BEDROOMS, POOL SAFETY |
| COMPLIANCE, AND SAFETY GLASS COMPLIANCE. |
| |
| 4.ENERGY CALCS REQUIRED FBC13-101.2. |
| |
| 5.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE |
| STAMPED AND THE RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION.233-5025 |
| |
| 6.)PROVIDE CALCULATIONS FOR THE |
| REAR ELEVATION TO SHOW COMPLIANCE WITH |
| TABLE 600 (20% MAX OF OPENINGS, TYPE |
| VI CONSTRUCTION UNPROTECTED). |
| |
| 7.)THE ADDITION MUST COMPLY WITH |
| THE RESIDENTIAL SWIMMING POOL SAFETY |
| ACT 515 FS. |
| |
| 8.)SOFFIT VENTS ARE TO COMPLY WITH |
| FBC 2309.7, CANNOT "MATCH EXISTING". |
| SPECIFY SIZE AND SPACING OR NUMBER. |
| |
| 9.)ATTIC ACCESS REQUIED, FBC2309.6. |
| |
| 10.)SPECIFY CEILING INSULATION ON THE |
| WALL SECTION (A5).BEFORE RESUBMITTING, |
| BE SURE THAT THE INSULATION ON THE PLAN |
| IS CONSISTENT WITH THE MINIMUMS ON THE |
| ENERGY CALCS. |
| |
| 11.)FIRESTOP REQUIRED, FBC 705.5 |
| (REVISE WALL SECTION A5). |
| |
| 12.)ADDITIONAL FEES REQUIRED. |