Plan Review Notes
Plan Review Notes For Permit 03052306
Permit Number 03052306
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-11 00:00:00******CORRECTIONS*******
  
 1.)ADDITIONAL PERMITS REQUIRED.
  
 2.)WINDOW B IS REQUIRED TO BE SAFETY
 GLASS, FBC2405.2.1.
  
 3.)PROVIDE AREA CALCULATIONS ON THE
 PLAN.IF THE ADDITION AREA IS GREATER
 THAN 25% OF THE EXISTING, COMPLY WITH
 FBC 3401.7.1.SHOW EMERGENCY EGRESS
 FOR BEDROOMS, SMOKE DETECTORS FOR
 EXISTING BEDROOMS, POOL SAFETY
 COMPLIANCE, AND SAFETY GLASS COMPLIANCE.
  
 4.ENERGY CALCS REQUIRED FBC13-101.2.
  
 5.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.233-5025
  
 6.)PROVIDE CALCULATIONS FOR THE
 REAR ELEVATION TO SHOW COMPLIANCE WITH
 TABLE 600 (20% MAX OF OPENINGS, TYPE
 VI CONSTRUCTION UNPROTECTED).
  
 7.)THE ADDITION MUST COMPLY WITH
 THE RESIDENTIAL SWIMMING POOL SAFETY
 ACT 515 FS.
  
 8.)SOFFIT VENTS ARE TO COMPLY WITH
 FBC 2309.7, CANNOT "MATCH EXISTING".
 SPECIFY SIZE AND SPACING OR NUMBER.
  
 9.)ATTIC ACCESS REQUIED, FBC2309.6.
  
 10.)SPECIFY CEILING INSULATION ON THE
 WALL SECTION (A5).BEFORE RESUBMITTING,
 BE SURE THAT THE INSULATION ON THE PLAN
 IS CONSISTENT WITH THE MINIMUMS ON THE
 ENERGY CALCS.
  
 11.)FIRESTOP REQUIRED, FBC 705.5
 (REVISE WALL SECTION A5).
  
 12.)ADDITIONAL FEES REQUIRED.