Plan Review Notes
Plan Review Notes For Permit 03052278
Permit Number 03052278
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-21 00:00:00DENIED;
 RISER DIAGRAM DOES NOT MATCH FLOOR PLAN
 AND IS NOT TO CODE.
 1.SECOND FLOOR BATHROOM REQUIRES IT'S
 OWN WASTE STACK IT CANNOT DUMP INTO
 VENT STACK FOR FIRST FLOOR BATHROOM.
 2.FLOOR PLAN SHOWS TUB ON SECOND FLOOR
 NOT SHOWER.
 3.FIRST FLOOR OFFICE BATHROOM FLOOR PLAN
 SHOWS TUB RISER DIAGRAM SHOWS SHOWER.
 4.MASTER BATHROOM, RISER DIAGRAM SHOWS
 2- SHOWERS AND 3- LAVS. FLOOR PLAN
 SHOWS 1-TUB, 1-SHOWER AND 2-LAVS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695