Plan Review Notes For Permit 03052278 |
Permit Number |
03052278 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-13 00:00:00 | FAILED | | ~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE NECESSARY CHANGES ON | | PLANS AND RESUBMIT FOR REVIEW. | | | | 1}NOTE THAT THERE ARE TWO AHU'S ON THE | | PANEL SCHEDULE AND ONLY ONE LISTED IN | | THE CALCULATIONS. | | | | 2}PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 3}PLEASE NOTE THAT DISCONNECTS MUST | | COMPLY WITH 110-26. | | | | 4}PLEASE NOTE FRONT AND REAR | | RECEPTS REQ'D PER 210-52E. | | | | 5}PLEASE SHOW THE REQ'D BATH(S) | | RECEPTACLES PER 210-52(D). | | | | 6}THE AHU CLOSET IS MISSING IN THE ATTIC | | STORAGE ROOM. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|