2003-07-08 00:00:00 | ******CORRECTIONS******** |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2.)THE ORIGINAL RECEIPT SHOWING THAT |
| IMPACT FEES HAVE BEEN PAID MUST BE |
| ATTACHED TO THE APPLICATION. |
| |
| 3.)THE AREA CALCULATIONS SHOULD SHOW |
| SUBTOTALS FOR CONDITIONED AND UNCONDIT. |
| SPACE.IMPACT FEES WERE PAID ON A |
| SQUARE FOOTAGE LESS THAN THE TOTAL A/C |
| SQUARE FOOTAGE.CALL 233-5025 TO |
| DETERMINE WHETHER OR NOT IMPACT FEES |
| NEED TO BE ADJUSTED. |
| |
| 4.)THE TOTAL CONDITIONED FLOOR AREA |
| ON THE ENERGY CALC IS INCORRECT. |
| |
| 5.)ADDITIONAL FEES ARE DUE (VALUE |
| ADJUSTMENT); $755.07. |
| |
| 6.)PROVIDE A SOILS INVESTIGATION |
| REPORT. |
| |
| 7.)THE 2ND FLOOR BATHROOM WINDOW MUST |
| COMPLY WITH FBC 2405.1 (SAFETY GLASS). |
| |
| 8.)PROVIDE DETAILS FOR THE GUARDRAIL |
| AND THE STAIR RAIL, GIVING ALL |
| DIMENSIONS AND SHOWING COMPLIANCE WITH |
| FBC 1608.2. |
| |
| 9.)PROVIDE A ROOF SHEATHING ATTACHMENT |
| SCHEDULE. |
| |
| 10.) SHOW THE FIRESTOP FOR THE FRAME |
| WALL, FBC 705.3. |
| |
| 11.)THE ENERGY CALC DOES NOT SHOW THE |
| 2X6 EXTERIOR FRAME WALL.PROVIDE A |
| WALL LEGEND. |
| |
| 12.)FOR CLARIFICATION, EXPLAIN THE |
| DIFFERENCE BETWEEN COLUMN A AND COLUMN |
| B.THE TEXT DESCRIPTIONS ARE THE SAME. |
| (SHEET 6). |
| |
| 13.)THE 2ND FLOOR PLAN (SHEET 4) SHOWS |
| FRENCH DOORS AT THE OPEN AREA.SHEET |
| 7 SHOWS S/H WINDOWS AT THAT LOCATION. |
| |
| 14.)SHOW INSULATION FOR THE ADJACENT |
| WALL, SHEET 6. |
| |
| 15.)THE SQUARE FOOTAGE FOR 10A ON THE |
| ENERGY CALC IS INCORRECT. |
| |
| 16.)THE FOLLOWING PRODUCT APPROVALS |
| ARE NOT LEGIBLE: |
| PREMDOOR |
| GARAGE DOOR |
| SHUTTERS |
| PROVIDE TWO LEGIBLE COPIES.SEE |
| ATTACHED FOR INSTRUCTIONS TO OBTAIN |
| PRODUCT APPROVALS ONLINE. |
| |
| 17.)THE FOLLOWING PRODUCT APPROVALS |
| ARE REQUIRED BUT WERE NOT SUBMITTED: |
| DOUBLE FRENCH DOOR (UNLESS PREMDOOR |
| IS USED IN ALL OF THE LOCATIONS) |
| SINGLE FRENCH DOOR |
| GLASS BLOCK |
| MULLIONS |
| EXTERIOR SIDE DOOR |
| |
| 18.)THE REPORT FOR THE FIXED GLASS |
| WINDOWS USED ASTM E330-90 AS THE |
| STRUCTURAL TEST.FBC35 SPECIFIES |
| ASTM E330-84.SUBMIT TWO COPIES OF |
| PRODUCT APPROVALS FOR THE FIXED GLASS |
| WINDOW. |
| |
| WHEN RESUBMITTING, REPLACE ANY SHEETS |
| WHICH HAVE CHANGED WITH NEW SHEETS. |
| SUBMIT THE OLD SHEETS SEPARATELY, |
| MARKED.SUBMIT THIS CORRECTION LIST |
| WITH A WRITTEN EXPLANATION AS TO HOW |
| EACH ITEM WAS ADDRESSED.ALL CHANGES |
| SHOULD BE CLEARLY MARKED WITH EITHER |
| CLOUDS OR TRIANGLES. |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |