2003-07-18 00:00:00DENIED BY BUILDING
  
 1) THE SITE SPECIFIC ENGINEERING DOES
 NOT CORRESPOND TO THE WINDOW SIZES ON
 THE PLANS. THE JOB/SITE LOCATION IS NOT
 LISTED ON THE FORM. THE DESIGNER OF
 RECORD IS REQUIRED TO SIGN AND SEAL THE
 FORM OR PROVIDE A SIGNED AND SEALED
 LETTER REFERENCING THE PRODUCTS AND
 JOB LOCATION.
  
 2) SUBMIT A LETTER FROM AL-FAROOQ CORP.
 (SIGNED AND SEALED) STATING THAT THE
 SITE SPECIFIC DRAWINGS FOR THE MULLIONS
 HAVE BEEN REVIEWED AND APPROVED BY THEM
 AS REQUIRED BY THE PRODUCT EVALUATION
 DOCUMENT THAT WAS SUBMITTED. SEE NOTES
 #3 AND D ON DRAWING NO. M96-08B. SHEET 1
 OF 3.
  
 3)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLASS BLOCK
 - 16' WIDE GARAGE DOOR
 - DOUBLE OUTSWING FRONT DOORS
 - STORM PANELS
  
 4)THE PRELIMINARY SOIL REPORT RECOMMENDS
 ADDITIONAL TESTING. CONTRACTOR WILL BE
 CONTINUING AT HIS OWN RISK WITHOUT
 ADDITIONAL TESTING.
  
 5) STRUCTURE IS LOCATED IN AN "A0" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 6) THE ROOF SLOPE ON THE KNEZEVICH
 SCHEDULE FOR THE STORM PANELS HAS THE
 WRONG ROOF PITCH LISTED. THE PLANS
 SPECIFY A 5 INCH PER FOOT ROOF SLOPE.
 THE NEGATIVE PRESSURE FOR OPENING #14
 IS HIGHER ON THE KNEZEVICH SCHEDULE THAN
 LISTED ON THE INSTALLATION SCHEDULE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714