2003-07-18 00:00:00 | DENIED BY BUILDING |
| |
| 1) DETAIL 11 ON A5 SPECIFIES A HANGER |
| FASTENED TO A MASONRY WALL WITH (2) 5/8" |
| THROUGH BOLTS ON EACH SIDE. PLEASE |
| CORRECT. |
| |
| 2) THE PRODUCT APPROVAL FOR THE GARAGE |
| DOOR IS MISSING PAGES AND THE DRAWING IS |
| NOT LEGIBLE. |
| |
| 3) THE PRODUCT APPROVAL FOR THE DOUBLE |
| OUTSWING DOOR IS ILLEGIBLE. |
| |
| 4) THE PRODUCT APPROVAL FOR THE SLIDING |
| GLASS DOOR IS MISSING PAGS 4-6 OF THE |
| APPROVED DRAWINGS. |
| |
| 5)THE PRELIMINARY SOIL REPORT RECOMMENDS |
| ADDITIONAL TESTING. CONTRACTOR WILL BE |
| CONTINUING AT HIS OWN RISK WITHOUT |
| ADDITIONAL TESTING. |
| |
| 6) THE SITE SPECIFIC ENGINEERING DOES |
| NOT LIST WINDOW #11 FROM THE PLANS. THIS |
| IS THE 96"X 72" F.G. WINDOW WITH THE |
| 96"X 23" F.G. ABOVE IT. THE NEGATIVE |
| WINDLOAD PRESSURE LISTED ON THE PLANS |
| FOR WINDOWS #14 AN #15 (-45.3PSF) |
| EXCEEDS THE DESIGN PRESSURE SPECIFIED ON |
| THE SITE SPECIFIC PRODUCT APPROVAL. |
| |
| 7) SUBMIT A SIGNED AND SEALED LETTER |
| FROM AL-FAROOQ CORPORATION STATING THAT |
| THE SITE SPECIFIC DRAWINGS FOR THE |
| MULLIONS HAVE BEEN REVIEWED AND APPROVED |
| BY THEM AS REQUIRED BY THE PRODUCT |
| EVALUATION DOCUMENT THAT WAS SUBMITTED. |
| SEE NOTES #3 AND D ON DRAWING NUMBER |
| M96-08B SHEET 1 OF 3. |
| |
| 8) THE SLOPE ON THE KNEZEVICH WINDLOAD |
| SCHEDULE IS INCORRECT. THE PLANS |
| INDICATE A 5/12 PITCH. THE STORM PANEL |
| INSTALLATION SCHEDULE LISTS A PRESSURE |
| OF -74.9 PSF FOR OPENINGS 5,6 AND 14, |
| WITH PANEL LENGTHS OF 108". THE MAXIMUM |
| PRESSURE LISTED ON THE PRODUCT APPROVAL |
| IS -74.3PSF FOR PANELS UP TO 70" IN |
| LENGTH AND -72 FOR ALL OTHERS. SEE PAGES |
| 13, 14 AND 15 OF THE PRODUCT APPROVAL. |
| SUBMIT CORRECT INSTALLATION SCHEDULE OR |
| APPLY UNDER A SEPARATE PERMIT. |
| |
| 9) STRUCTURE IS LOCATED IN A "AO" FLOOD |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |