Plan Review Notes
Plan Review Notes For Permit 03052092
Permit Number 03052092
Review Stop M
Sequence Number 1
Notes
Date Text
2003-06-24 00:00:00DENIED:
  
 ENERGY CALCS INDICATE 11 SEER AND THE
 EQUIPMENT PLAN INDICATED ON THE PLAN
 SHOWS 10 SEER.PLEASE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved