2003-08-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03052070
 ADD: 409 NORTHPOINT PARKWAY
 CONT: LTI DEVELOPMENT
 TEL: (561)718-6243
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) FIRST REVIEW THE MAJOR OCCUPANCY WAS
 LISTED AS BUSINESS. THE BUSINESS CLASSIF
 ICATION MET THE CRITERIA FOR SINGLE
 MEANS OF EGRESS, FIRST FLOOR, UNDER
 3,500 SQ FT, LESS THAN 75' TRAVEL DISTAN
 CE, THE WALL SEPERATING THE OFFICE FROM
 STORAGE 2 HR RATED.
  
 THE SECOND REVIEW, THE MAJOR OCCUPANCY
 IS MERCANTILE, SINGLE EXIT REQUIREMENTS,
 1025.1 MAXIMUM ONE STORY, FLOOR AREA TO
 NOT EXCEED 2,250 SQ FT TRAVEL DISTANCE
 NOT TO EXCEED 50'.
  
 THE MERCANTILE DOES MEET THE REQUIRE-
 MENTS FOR SINGLE EXIT.
 1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.FULLY
 SPRINKLERED 1/3RD THE DISTANCE.
  
 MERCANTILE OCCUPANCY WILL REQUIRE A
 SECOND MEANS OF EGRESS, NOT THROUGH THE
 WAREHOUSE, UNLESS SEPERATED BY AND
 ENCLOSED RATED 1 HR MEANS OF EGRESS TO
 THE EXTERIOR.
  
 THE WAREHOUSE ALSO WILL NEED 2 MEANS OF
 EGRESS, THE DOORWAY INTO THE LOUNGE AREA
 WILL DO BUT A EXIT LIGHT WILL BE NEEDED
 AT THE WAREHOUSE SIDE OF THE DOOR
 1016.1.1.
  
 2) OCCUPANCY SEPERATION: STORARE VS.
 BUSSINESS: 2 HR WITH 1 1/2 HR DOORS.
 704.1.2.2.(4)SEPERATION OF MERCANTILE TO
 STORAGE WOULD NOT BE REQUIRED IF THE
 STORAGE AREA WERE LESS THAN 1/3RD OF THE
 MAJOR OCCUPANCY (MERCANTILE).
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026