Plan Review Notes
Plan Review Notes For Permit 03051999
Permit Number 03051999
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) BREAK ROOM SINK SHALL COMPLY WITH
 11-4.24 AND ALL SUBSECTIONS. SHOW CLEAR
 FLOOR SPACE, HEIGHT OF SINK, KNEE CLEAR-
 ANCE, ECT.
 2) BATHROOM SHALL COMPLY WITH 11-4.23 &
 ALL SUBSECTIONS. SHOW CLEAR FLOOR SPACE,
 DOOR SWING SHALL NOT OPEN INTO CLEAR
 FLOOR SPACE OF ANY FIXTURE, HEIGHT OF
 GRAB BARS FOR TUB, SEAT FOR TUB, CONT-
 ROLS, AND SHOWER UNIT. PLEASE SUBMIT A
 DETAIL.
 3) TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. (ALSO SEE 410.1)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692