Plan Review Notes For Permit 03051988 |
Permit Number |
03051988 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-05-31 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. | | 2. TYPE OF GAS, (LP OR NATURAL) | | 3. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | THRU 402.5.2 AND TABLES 402(1) THRU | | 402(34). | | 4. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | 5) INDICATE WHICH CHARTS WERE USED TO | | SIZE THE PIPE. CHARTS FROM THE 97 STAND- | | ARD GAS CODE INDICATE THAT THE SIZING | | IS WRONG. TABLE 305.4A INDICATE THAT | | ONLY 50,000 BTU'S ALLOWED ON 3/4" SCHED. | | 40, AND ONLY 340,000 BTU'S ALLOWED FOR | | 1-1/2". - ALSO TABLE 305.4E INDICATES | | THAT ONLY 310,000 BTU'S ALLOWED FOR | | 1-1/2" PE PIPE. AND ONLY 62,000 BTU'S | | ALLOWED FOR 3/4" PE PIPE. PLEASE CLAIRFY | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|