Plan Review Notes
Plan Review Notes For Permit 03051988
Permit Number 03051988
Review Stop P
Sequence Number 1
Notes
Date Text
2003-05-31 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5) INDICATE WHICH CHARTS WERE USED TO
 SIZE THE PIPE. CHARTS FROM THE 97 STAND-
 ARD GAS CODE INDICATE THAT THE SIZING
 IS WRONG. TABLE 305.4A INDICATE THAT
 ONLY 50,000 BTU'S ALLOWED ON 3/4" SCHED.
 40, AND ONLY 340,000 BTU'S ALLOWED FOR
 1-1/2". - ALSO TABLE 305.4E INDICATES
 THAT ONLY 310,000 BTU'S ALLOWED FOR
 1-1/2" PE PIPE. AND ONLY 62,000 BTU'S
 ALLOWED FOR 3/4" PE PIPE. PLEASE CLAIRFY
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692