Notes
Date Text
2003-07-07 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 03051869
 ADDRESS: 2355 MORGANS BLUFF
 CONT: SIERRA CONSTRUCTION
 TELL # (786)236-5362
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 *****PROVISO******
  
 1)R-3 EGRESS DOOR/ 32" CLEAR:
 1003.2.1. THE WIDTH OF THE MEANS OF
 EGRESS SHALL BE DETERMINED FROM THE
 OCCUPANTS SERVED IN ACCORDANCE WITH
 TABLE 1004.R-3 MINIMUM CLEAR OPENING OF
 EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS
 USED IN THE EXIT ACCESS SHALL PROVIDE A
 CLEAR OPENING OF NOT LESS THAN 32" WIDE.
 1012.1.7 REQUIRED EXIT DOORS SHALL BE
 OPENABLE FROM THE INSIDE WITHOUT THE USE
 OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR
 EFFORT. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE PROHIBITED. ALL HARD-
 WARE MUST BE DIRECT ACTING REQUIRING NO
 MORE THAN ONE OPERATION.
  
 REVIEW FRONT ENTRY, REVISE BEFORE BUCK
 INSPECTION.
  
 2) STORM SHUTTERS:
 A) MISSING KEY PLAN
 B) BOTTOM FASTENER, CAULK-IN, THE VALUE
 TAKEN FOR CONCRETE, NOT CEMENT BLOCK,
 OR IF THIS VALUE IS TO BE TAKEN FOR
 FILLED CELL THE CAULK-IN MUST BE SET IN
 2500 PSI CONCRETE. OTHER ALTERNATIVE IS
 A DIFFERENT FASTENER FOR BLOCK.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 805-6715