Plan Review Notes For Permit 03051857 |
Permit Number |
03051857 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-07-01 00:00:00 | | | *** ISSUED PERMIT*** | | -PLAN REVIEW HISTORY- | | | | PERMIT# 03051857 | | ADDRESS: 8719 S SAN ANDROS | | CONT: SIERRA CONT | | TELL # (786)236-5312 | | | | THE ATTACHED COMMENTS ARE PART OF THE | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | ******PROVIDO***** | | 1)PROVIDE NEW PRODUCT APPROVAL AND | | REVISE PLANS FOR THE FRONT ENTRY DOOR | | BEFORE BUCK INSPECTION, TO COMPLY WITH: | | R-3 EGRESS DOOR/ 32" CLEAR: | | 1003.2.1. THE WIDTH OF THE MEANS OF | | EGRESS SHALL BE DETERMINED FROM THE | | OCCUPANTS SERVED IN ACCORDANCE WITH | | TABLE 1004.R-3 MINIMUM CLEAR OPENING OF | | EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS | | USED IN THE EXIT ACCESS SHALL PROVIDE A | | CLEAR OPENING OF NOT LESS THAN 32" WIDE. | | 1012.1.7 REQUIRED EXIT DOORS SHALL BE | | OPENABLE FROM THE INSIDE WITHOUT THE USE | | OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR | | EFFORT. MANUALLY OPERATED FLUSH BOLTS OR | | SURFACE BOLTS ARE PROHIBITED. ALL HARD- | | WARE MUST BE DIRECT ACTING REQUIRING NO | | MORE THAN ONE OPERATION. |
|