2003-07-09 00:00:00 | |
| *** ISSUED PERMIT*** |
| -PLAN REVIEW HISTORY- |
| |
| PERMIT# 03051851 |
| ADDRESS: 8853 S. SAN ANDROS |
| CONT: SIERRA |
| TELL # (786)236-5312 |
| |
| THE ATTACHED COMMENTS ARE PART OF THE |
| PERMIT AND PLAN REVIEW PACKAGE AND ARE |
| NOT TO BE REMOVED FROM THE ISSUED SET OF |
| PLANS.104.2.1.2 ADMINISTRATIVE CODE. |
| *****PROVISO****** |
| 1) ZERO LOT SIDE OF PROPERTY REQUIRES A |
| EGRESS ACCESS EASEMENT BEFORE C/O. |
| |
| 2) PROVIDE NEW PRODUCT APPROVAL AND |
| REVISE PLANS FOR THE FRONT ENTRY DOOR |
| BEFORE BUCK INSPECTION, TO COMPLY WITH: |
| R-3 EGRESS DOOR/ 32" CLEAR: |
| 1003.2.1. THE WIDTH OF THE MEANS OF |
| EGRESS SHALL BE DETERMINED FROM THE |
| OCCUPANTS SERVED IN ACCORDANCE WITH |
| TABLE 1004.R-3 MINIMUM CLEAR OPENING OF |
| EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS |
| USED IN THE EXIT ACCESS SHALL PROVIDE A |
| CLEAR OPENING OF NOT LESS THAN 32" WIDE. |
| 1012.1.7 REQUIRED EXIT DOORS SHALL BE |
| OPENABLE FROM THE INSIDE WITHOUT THE USE |
| OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR |
| EFFORT. MANUALLY OPERATED FLUSH BOLTS OR |
| SURFACE BOLTS ARE PROHIBITED. ALL HARD- |
| WARE MUST BE DIRECT ACTING REQUIRING NO |
| MORE THAN ONE OPERATION. |
| |
| 3) A) KEY PLAN FOR SHUTTER OPENINGS. |
| B) BOTTOM FASTENER CAULK-IN, THE VALUE |
| TAKEN IS FOR CONCRETE, NOT CEMENT BLOCK! |
| THIS FASTENER MAY NOT BE USED IN BLOCK, |
| OR IF THIS IS USED IN FILLED CELL, THE |
| CAULK-IN MUST BE IN 2500 PSI CONCRETE |
| (FILLED CELL). OTHER ALTERNATIVE IS A |
| DIFFERENT FASTENER FOR BLOCK. |
| |