2003-06-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051851
 ADD: 8853 S. SAN ANDROS
 CONT: SIERRA CONST
 TEL: (561)616-9686
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 THE TESING REPORT IS FOR ANDROS ISLES
 PARCEL "E2" PLAT1.THE PARCEL IN QUESTION
 IS "E2" PLAT2.
  
 3) TABLE 600 ISSUE, GLASS BLOCK, PROVIDE
 DOCUMENTATION FOR 1 HR RATING, 0-3' FROM
 THE PROPERTY LINE. THIS IS NOT CONSIDER-
 ED OPENING BUT WALL 1HR RATING.
  
 4) PLANS INDICATE THEUSE OF STORM
 SHUTTRS FOR WINDOWS AND SIDELITES BUT
 NO STORM SHUTTER INFORMATION ATTACHED.
 MISSING PRODUCT APPROVAL, KEY PLAN
 AND INSTALLATION SCHEDULE, SEE ATTACH-
 MENT FOR SAMPLE.
  
 4) 1606.1.7 REQUIRED WIND DESIGN
 INFORMATION, MISSING THE INTERNAL
 PRESSURE COEFFICIENT. WITHOUT THIS IT
 IS ONLY ASSUMED THAT IT IS A CLOSED
 BUILDING.
 CLOSED BUILDING+-.18
 PARTIAL ENCLOSED +-.55
 OPEN +-.0
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.