Plan Review Notes
Plan Review Notes For Permit 03051845
Permit Number 03051845
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-27 00:00:00BUILDING DENIED
  
 1) SUBMIT SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMEND. TO FBC 1804.2.2.
 THE ONE SUBMITTED IS FOR THE WRONG
 PARCEL.
  
 2) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE AN ELEVATION CERTIFICATE
 WILL BE REQUIRED PRIOR TO C.O.
  
 3) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED AT THE ZERO LOT LINE. FBC
 TABLE600 REQUIRES ONE HOUR RATED WALL
 WITH NOOPENINGS WITHIN 3' OF PROPERTY
 LINE. GLASS BLOCK IS CONSIDER A WALL
 COMPONENT AND NOT AN OPENING IF IT HAS
 A MIN. ONE HOUR FIRE RATING. SUBMIT
 MANUFACTURER'S SPECIFICATIONS & LISTING
 INFORMATION FOR ONE HOUR RATED GLASS
 BLOCK.
  
 4) FBC 1606.1.7 REQUIRES SPECIFIC DESIGN
 WINDLOAD INFORMATION ON THE PLANS.
 PLEASE INDICATE THE INTERNAL PRESSURE
 COEFFICENT ON S-3.
  
 5) THE DOUBLE FRONT DOOR DOES NOT COMPLY
 WITH EGRESS REQUIREMENTS. EXIT DOOR MUST
 BE OF THE SIDE SWINGING TYPE WITH A MIN.
 CLEAR OPENING OF 32". SEE FBC TABLE 1004
 AND SECTIONS 1003.2.3.1 AND 1012.1.
  
 6) INDICATE THE LOCATIONS AND MATERIALS
 FOR THE DRAFTSTOPPING THAT IS REQUIRED
 AT THE FLOOR/CEILING ASSEMBLY. SEE FBC
 2305.2.2.
  
 7) DETAIL 2 ON S-5 AND SECTION D-D ON
 S-5 FOR THE GIRDER HANGER APPEAR TO BE
 IN ERROR. THE CEILING HEIGHT (BOTTOM OF
 GIRDER) IS 10' THE TOP OF THE BOND BEAM
 IS AT 10'-8". THE TOP ANCHOR HOLE IS AT
 11',WHICH WILL BE ABOVE THE BOND BEAM.
 SHEET S-1 INDICATES FILLED CELLS BELOW
 THE BOND BEAM BUT NOT ABOVE IT. PLEASE
 CORRECT.
  
 8) FBC 1609.4 NO LONGER ALLOWS THE ONE-
 THIRD INCREASE ON STEEL CALCULATIONS.
 PLEASE REVISE THE CONNECTOR SCHEDULE ON
 SHEET S-3. THE VALUES FOR THE SIMPSON
 H-16, HETAL20, META16, AND USP RT24T ARE
 INCORRECT. SEE THE 2003 USP AND 2002
 SIMPSON HIGH-WIND RESISTANT CONSTRUCTION
 CATALOGS.
  
 9)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - THE FIXED GLASS TOMBSTONE (K) AND
 ROUND (N) WINDOWS.
 - HORIZONTAL SLIDING WINDOW (EXPIRED ON
 3-17-03)
 - GARAGE DOOR (THE REQUIRED NEGATIVE
 PRESSURE LISTED ON THE PLANS EXCEEDS
 THE DESIGN PRESSURE ON THE PRODUCT
 APPROVAL)
 - THE DOUBLE FRONT DOOR (THE REQUIRED
 NEG. PRESSURE EXCEEDS THE PRODUCT
 DESIGN PRESSURE)
  
 10) SUBMIT AN INSTALLATION SCHEDULE AND
 A KEY PLAN FOR THE STORM PANELS. SPECIFY
 THE CONNECTION TYPE. NOTE: HOLLOW
 CONCRETE BLOCK WITH POWERS CALK-IN
 ANCHORS ARE NOT ALLOWED FOR SOME
 CONNECTION TYPES. SEE SHEET 8 OF THE
 PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714