Plan Review Notes For Permit 03051835 |
Permit Number |
03051835 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-20 00:00:00 | | | BUILDING PLAN REVIEW | | PERMIT: 03051835 | | ADD: 2335 MORGANS BLUFF | | CONT: SIERRA CONSTRUCTION | | TEL: (561)616-9686 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | ACTION: DENIED | | | | 1) FL BLD CODE 1804.2.2 QUESTIONABLE | | SOILS, WHERE THE BEARING CAPACITY IS | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | THE TEST REPORT SUBMITTED IS FOR ANDROS | | ISLES PARCEL "E2" PLAT 1 NOT PARCEL"E2" | | PLAT 2. | | | | 2) TABLE 600 ISSUE, GLASS BLOCK, | | PROVIDE 1 HR FIRE RATING FOR GLASS BLOCK | | MANUFACTURES SPEC, THE OPENINGS ARE CONS | | IDERED WALL SINCE LOCATED 0-3' FROM PROP | | ERTY LINE, NO OPENINGS ALLOWED. | | | | 3) PLANS INDICATE THE USE OF STORM | | SHUTTERS FOR WINDOWS AND SIDELITES. | | NO KEY PLAN OR INSTALLATION SCHEDULE. | | THE OTHER ISSUE IS THAT THE CONNECTION | | #1 IS HIGHLIGHTED, THE TABLES INDICATE | | THE USE OF 1/4" CALK-INS IN MASONARY, | | USING THIS TYPE OF CONNECTION THE REPORT | | INDICATES THIS CONNECTION IS NOT | | APPROVED. | | | | 4) 1606.7.1 REQUIRED WIND DESIGN INFOR- | | MATION, MISSING THE INTERNAL PRESSURE | | COEFFICIENT. WITHOUT THIS IT IS ONLY AND | | ASSUMPTION THAT THIS IS A CLOSED BUILD- | | ING. | | | | CLOSED BUILDING +-.18 | | PARTIAL ENCLOSD +-.55 | | OPEN+-.0 |
|