Plan Review Notes
Plan Review Notes For Permit 03051826
Permit Number 03051826
Review Stop P
Sequence Number 2
Notes
Date Text
2003-07-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMID. CODE
  
 1) THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN NOR DOES IT MEET
 CODE REQUIREMENTS.
 2) BATH #3 SHOW 4 LAVS ON RISER AND ONLY
 2 ON THE FLOOR PLAN.
 3) BATH #4, ONLY THE FIXTURES IN THE
 BATHROOM GROUP SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. A SEPAR-
 ATE STACK FOR BAR SINK SHALL TIE IN
 DOWNSTREAM OF THE BATHROOM FIXTURES.
 SECTION 909.1
 4) BATH #1 FROM PREVIOUS REVIEW, THE
 LAUNDRY SINK AND WASH MACHINE SHALL TIE
 IN DOWNSTREAM OF THE BATHROOM FIXTURES.
 SECTION 909.1. ALSO SEE ATTACHED SHEET
 TO PREVIOUS REVIEW FOR EXAMPLE OF HOW
 THE LAUNDRY ROOM/BATHROOM #1 SHOULD BE
 PIPED FOR CODE COMPLIANCE AND TO REFLECT
 THE FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692