2003-07-19 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 AMENDMENTS, CHAPTER | | ONE, ADMID. CODE | | | | 1) THE SANITARY RISER DIAGRAM DOES NOT | | REFLECT THE FLOOR PLAN NOR DOES IT MEET | | CODE REQUIREMENTS. | | 2) BATH #3 SHOW 4 LAVS ON RISER AND ONLY | | 2 ON THE FLOOR PLAN. | | 3) BATH #4, ONLY THE FIXTURES IN THE | | BATHROOM GROUP SHALL CONNECT TO THE WET- | | VENTED HORIZONTAL BRANCH DRAIN. A SEPAR- | | ATE STACK FOR BAR SINK SHALL TIE IN | | DOWNSTREAM OF THE BATHROOM FIXTURES. | | SECTION 909.1 | | 4) BATH #1 FROM PREVIOUS REVIEW, THE | | LAUNDRY SINK AND WASH MACHINE SHALL TIE | | IN DOWNSTREAM OF THE BATHROOM FIXTURES. | | SECTION 909.1. ALSO SEE ATTACHED SHEET | | TO PREVIOUS REVIEW FOR EXAMPLE OF HOW | | THE LAUNDRY ROOM/BATHROOM #1 SHOULD BE | | PIPED FOR CODE COMPLIANCE AND TO REFLECT | | THE FLOOR PLAN. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 |
|