2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT 1, SANITARY RISER DIAGRAM DOES
 NOT MEET CODE OR REFLECT THE FLOOR PLAN.
 FLOOR PLANS SHOW W/C AND SHOWER, BUT THE
 RISER DIAGRAM SHOWS NO W/C AND AN EXTRA
 TUB. MASTER BATH BIDET NOT VENTED. 908.3
 BATH #1 ONLY THE FIXTURES FROM THE BATH
 ROOM GROUP SHALL DRAIN INTO THE WET VENT
 OF THE BATHROOM FIXTURES. THE TUB AND
 LAUNDRY SHALL TIE INTO BRANCH LINE PRIOR
 TO BATH #1, AND LAUNDRY SINK AND WASH
 MACHINE SHALL REQUIRE SEPARATE STACKS AS
 THEY ARE ON DIFFERENT WALLS. BATHS #'S
 2 & 4 SHOW TUBS ON FLOOR PLAN BUT HAVE
 SHOWERS ON RISER DIAGRAM. SEC 1-4.2.1
 SEC 909.1
 2) SHT 2 SHOWS GAS RANGE IN KITCHEN.
 SEPARATE PLANS & PERMIT REQUIRED FOR GAS
 SECTION 104.2.1
 (SEE ATTACHED SHEET FOR BATH #1 - LAUN-
 DRY ROOM RISER EXAMPLE)
  