2003-06-16 00:00:00 | DENIED: | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW: | | | | 1.RETURN AIR - PLEASE PROVIDE GRILLE | | SIZES AND SIZE OF DUCTWORK.PLAN SHEET | | M3 AIR TERMINAL SCHEDULE, R/A "SEE SHEET | | FOR SIZES" - GRILLE SIZES ARE NOT SHOWN. | | | | 2.EXHAUST FANS ARE NOT IDENTIFIED AS | | PER SCHEDULE INDICATED ON PLAN SHEET M3. | | | | 3.PLEASE PROVIDE OUTSIDE AIR CALCS BY | | BY NATURAL MEANS (2001 FBC(M) 402.2) OR | | BY MECHANICAL MEANS (2001 FBC(M) TABLE | | 403.3). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|