Plan Review Notes
Plan Review Notes For Permit 03051826
Permit Number 03051826
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-18 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE STATE THE CORRECT AMPERAGE OF
 THE METER ENCLOSURE ON THE RISER
 DIAGRAM. 500 AMPS DOES NOT CORRELATE TO
 ANY U L LISTED METER ENCLOSURE.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3} PLEASE INDICATE THE NUMBER AND SIZE
 OF THE CONDUCTORS IN THE 8"X8" GUTTER.
  
 4} THE #4 JUMPER SHOWN IN THE GUTTER
 FORMS A PARALLEL GROUND PATH WITH THE
 NEUTRAL THAT IS APPARANTLY TO BE
 GROUNDED AT THAT POINT,AND MUST BE
 REMOVED.
  
 5} THE #2 GROUNDING ELECTRODE CONDUCTOR
 IS NOT SUFFICIENTLY SIZED FOR THE
 SERVICE,SEE 250-66.
  
 6} THE 1/0 CONDUCTORS ARE INCORRECT FOR
 250 AMP OVERCURRENT SHOWN FROM THE
 DISCONNECT TO THE PANEL"A".310-15(B)(6).
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12.
  
 8} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 9} A GFI MUST BE ADDED TO THE FRONT TO
 COMPLY WITH 210-52(E)
  
 10} THERE ARE TWO PANELS SHOWN ON THE
 RISER DIAGRAM AND ONLY ONE SHOWN ON THE
 PLAN.PLEASE SHOW ALL EQUIPMENT.
  
 11} ALL BATH RECEPTACLES MUST COMPLY
 WITH 210-52(D).SEE MASTER BATH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW