2003-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051815
 ADD: 8791 SOUTH SAN ANDROS
 CONT: SIERRA CONSTRUCTION
 TEL: (561)616-9616
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 NO SOILS BORING REPORT SUBMITTED GIVING
 THE SAFE MINIMUM BEARING VALUE.
  
 2) TABLE 600 ISSUE, PROVIDE 1 HR RATING,
 FOR GLASS BLOCK 0-3' FROM PROPERTY LINE
 NO OPENINGS IN WALL SO GLASS BLOCK WILL
 REQUIRE A 1 HR RATING!!!
  
 3) STORM SHUTTERS MISSING INSTALLATION
 SCHEDULE AND KEY PLAN. PRODUCT APPROVAL
 PLEAS BE AWARE OF TYPE OF FASTENERS INTO
 MAASONARY, TYPE OF CONNECTION, SOMEONE
 HAS HIGHLIGHTED CONNECTIONS (C_1) THAT
 THE CALK-INS ARE NOT RATED FOR THIS
 APPLICATION.
  
 4) 1606.1.7 REQUIRES WIND DESIGN INFORMA
 TION, MISSING THE INTERNAL PRESSURE
 COEFFICIENT.
 CLOSED BUILDING+-.18
 PARTIAL OPEN +-.55
 OPEN +-.0