Plan Review Notes For Permit 03051815 |
Permit Number |
03051815 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-20 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 03051815 | | ADD: 8791 SOUTH SAN ANDROS | | CONT: SIERRA CONSTRUCTION | | TEL: (561)616-9616 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | ACTION: DENIED | | | | 1) FL BLD CODE 1804.2.2 QUESTIONABLE | | SOILS, WHERE THE BEARING CAPACITY IS | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | NO SOILS BORING REPORT SUBMITTED GIVING | | THE SAFE MINIMUM BEARING VALUE. | | | | 2) TABLE 600 ISSUE, PROVIDE 1 HR RATING, | | FOR GLASS BLOCK 0-3' FROM PROPERTY LINE | | NO OPENINGS IN WALL SO GLASS BLOCK WILL | | REQUIRE A 1 HR RATING!!! | | | | 3) STORM SHUTTERS MISSING INSTALLATION | | SCHEDULE AND KEY PLAN. PRODUCT APPROVAL | | PLEAS BE AWARE OF TYPE OF FASTENERS INTO | | MAASONARY, TYPE OF CONNECTION, SOMEONE | | HAS HIGHLIGHTED CONNECTIONS (C_1) THAT | | THE CALK-INS ARE NOT RATED FOR THIS | | APPLICATION. | | | | 4) 1606.1.7 REQUIRES WIND DESIGN INFORMA | | TION, MISSING THE INTERNAL PRESSURE | | COEFFICIENT. | | CLOSED BUILDING+-.18 | | PARTIAL OPEN +-.55 | | OPEN +-.0 |
|