Plan Review Notes
Plan Review Notes For Permit 03051809
Permit Number 03051809
Review Stop E
Sequence Number 3
Notes
Date Text
2003-09-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 CORRECT THE ARCHITECTS TITLE BLOCK TO
 COMPLY WITH 61G1-16.004.
  
 THE RISER DIAGRAM SHOWS THE PANEL BEING
 FED FROM THE METER AND THE PLAN
 INDICATES A METER/MAIN,PLEASE CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved