Plan Review Notes
Plan Review Notes For Permit 03051809
Permit Number 03051809
Review Stop P
Sequence Number 2
Notes
Date Text
2003-09-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE
 FLORIDA ADMINISTRATION CODE.
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS.
 A) LAUNDRY SINK IS NOT VENTED. SECTION
 901.2.1
 B) WASH MACHINE REQUIRES A STANDPIPE.
 SECTION 802.4
 C) WASH MACHINE REQUIRES A TRAP. SECT-
 ION 1002.1
 D) SEE RED LINE CORRECTION ON REVISION.
 2) 61G1-16.004 ARCHETICTS LICENSE NUMBER
 IS REQUIRED ON EACH SHEET.
  
 REVIEW BY KEN STEVENS