Plan Review Notes For Permit 03051809 |
Permit Number |
03051809 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-09-10 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 AMENDMENTS, CHAPTER | | ONE | | FLORIDA ADMINISTRATION CODE. | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | CODE REQUIREMENTS. | | A) LAUNDRY SINK IS NOT VENTED. SECTION | | 901.2.1 | | B) WASH MACHINE REQUIRES A STANDPIPE. | | SECTION 802.4 | | C) WASH MACHINE REQUIRES A TRAP. SECT- | | ION 1002.1 | | D) SEE RED LINE CORRECTION ON REVISION. | | 2) 61G1-16.004 ARCHETICTS LICENSE NUMBER | | IS REQUIRED ON EACH SHEET. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|