Plan Review Notes
Plan Review Notes For Permit 03051808
Permit Number 03051808
Review Stop P
Sequence Number 2
Notes
Date Text
2003-09-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPT 1,
 FLORIDA ADMIN. CODE
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) SECTION 909.1 ONLY THE FIXTURES WITH
 IN THE BATHROOM GROUP SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN.
 ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. THE W/M AND
 L/T SHALL CONNECT DOWNSTREAM OF BATHROOM
 FIXTURES.
 B) THE LAVS IN THE MASTER BATHROOM ARE
 ON DIFFERENT WALLS AND CANNOT DRAIN TO A
 COMMON STACK. 104.2.1
 C) MINIMUM TRAP SIZE FOR WASH MACHINE
 IS 2". TABLE 709.1
 2) ARCHITECT'S LICENSE NUMBER REQUIRED
 ON TITLE BLOCK. 61G1-16.004
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]