Plan Review Notes For Permit 03051808 |
Permit Number |
03051808 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-09-10 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 AMENDMENTS, CHAPT 1, | | FLORIDA ADMIN. CODE | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | CODE REQUIREMENTS, NOR DOES IT REFLECT | | THE FLOOR PLAN. | | A) SECTION 909.1 ONLY THE FIXTURES WITH | | IN THE BATHROOM GROUP SHALL CONNECT TO | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. | | ANY ADDITIONAL FIXTURES SHALL DISCHARGE | | DOWNSTREAM OF THE WET VENT. THE W/M AND | | L/T SHALL CONNECT DOWNSTREAM OF BATHROOM | | FIXTURES. | | B) THE LAVS IN THE MASTER BATHROOM ARE | | ON DIFFERENT WALLS AND CANNOT DRAIN TO A | | COMMON STACK. 104.2.1 | | C) MINIMUM TRAP SIZE FOR WASH MACHINE | | IS 2". TABLE 709.1 | | 2) ARCHITECT'S LICENSE NUMBER REQUIRED | | ON TITLE BLOCK. 61G1-16.004 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|