Plan Review Notes
Plan Review Notes For Permit 03051808
Permit Number 03051808
Review Stop E
Sequence Number 2
Notes
Date Text
2003-09-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT THE RISER DIAGRAM
 SHOWS THE PANEL BEING FED DIRECTLY FROM
 THE METER AND THE PLAN INDICATES A
 METER MAIN ,PLEASE CORRELATE.
  
 PLEASE CORRECT THE ARCHITECTS TITLE
 BLOCK YO CONFORM WITH FAC. 61G1-16.004.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718