2003-07-10 00:00:00********BUILDING PROVISO*******
 PERMIT: 03051786
 ADD: 2415 CURLEY CUT
 CONT: SIERRA
 TEL: (561)616-9686
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE DESIGNER OF RECORD TO PROVIDE THE
 CORRECTED WIND PRESSURES (FOR "B" ZONE)
 BEFORE WINDOW & DOOR BUCK INSPECTION.
  
 2) CORRECT A/C SQ FT AREA FOR ENERGY
 EFFICIENCY CODE ( SAME AS PLANS)
  
 3) STORM SHUTTERS:
 A) PROVIDE KEY PLAN TO CORRELATE TO THE
 SHUTTER SCHEDULE.
 B) BOTTOM FASTENER CAULK-IN, THE VALUE
 TAKEN IS FOR CONCRETE, NOT CEMENT BLOCK!
 THIS FASTENER MAY NOT BE USED IN BLOCK,
 OR IF THIS IS USED IN FILLED CELL, THE
 CAULK-IN MUST BE IN 2500 PSI CONCRETE
 (FILLED CELL). OTHER ALTERNATIVE IS A
 DIFFERENT FASTENER FOR BLOCK.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026