Plan Review Notes
Plan Review Notes For Permit 03051786
Permit Number 03051786
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051786
 ADD: 2415 CURLEY CUT
 CONT: SIERRA CONST
 TEL: (561)616-9686
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY:FLOOR AREA, PLANS VS. ENERGY
 CALCULATIONS.
  
 2)R-3 EGRESS DOOR/ 32" CLEAR:
 1003.2.1. THE WIDTH OF THE MEANS OF
 EGRESS SHALL BE DETERMINED FROM THE
 OCCUPANTS SERVED IN ACCORDANCE WITH
 TABLE 1004.R-3 MINIMUM CLEAR OPENING OF
 EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS
 USED IN THE EXIT ACCESS SHALL PROVIDE A
 CLEAR OPENING OF NOT LESS THAN 32" WIDE.
 1012.1.7 REQUIRED EXIT DOORS SHALL BE
 OPENABLE FROM THE INSIDE WITHOUT THE USE
 OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR
 EFFORT. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE PROHIBITED. ALL HARD-
 WARE MUST BE DIRECT ACTING REQUIRING NO
 MORE THAN ONE OPERATION.
  
 3) ZERO LOT LINE, GLASS BLOCK: TABLE
 600, ZERO % OPENING WALL RATING 1HR
 FOR GLASS BLOCK, NOT 3/4 HR OPENING PRO-
 TECTIVES.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 (2) THE WIND IMPORTANCE FACTOR IS
 ACTUALLY A "B" DROPPING THE REQUIRED
 PRESSURES, SOME MODELS THIS EFFECT THE
 PRODUCT APPROVALS!!!!SEE DOOR# 6.
 (4) MISSING THE INTERNAL PRESSURE
 COEFFICIENT +- .18
  
 6)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 THE CONNECTOR SCHEDULE, VALUES HIGH
 FOR THE :
 SIMPSONHETAL 201365 NOT 1890
 SIMPSONLTS 16720 NOT775
  
 7) STORM SHUTTERS:
 A) KEY PLAN
 B) BOTTOM FASTENER CAULK-IN, THE VALUE
 TAKEN IS FOR CONCRETE, NOT CEMENT BLOCK!
 THIS FASTENER MAY NOT BE USED IN BLOCK,
 OR IF THIS IS USED IN FILLED CELL, THE
 CAULK-IN MUST BE IN 2500 PSI CONCRETE
 (FILLED CELL). OTHER ALTERNATIVE IS A
 DIFFERENT FASTENER FOR BLOCK.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026