2003-07-01 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 03051771
 ADDRESS: 2475 CURLEY CUT
 CONT: SEIRRA
 TELL # (786) 236-53121
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 *****PROVISO*****
  
 1) PROVIDE NEW PRODUCT APPROVAL AND
 REVISE PLANS FOR THE FRONT ENTRY DOOR
 BEFORE BUCK INSPECTION, TO COMPLY WITH:
 R-3 EGRESS DOOR/ 32" CLEAR:
 1003.2.1. THE WIDTH OF THE MEANS OF
 EGRESS SHALL BE DETERMINED FROM THE
 OCCUPANTS SERVED IN ACCORDANCE WITH
 TABLE 1004.R-3 MINIMUM CLEAR OPENING OF
 EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS
 USED IN THE EXIT ACCESS SHALL PROVIDE A
 CLEAR OPENING OF NOT LESS THAN 32" WIDE.
 1012.1.7 REQUIRED EXIT DOORS SHALL BE
 OPENABLE FROM THE INSIDE WITHOUT THE USE
 OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR
 EFFORT. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE PROHIBITED. ALL HARD-
 WARE MUST BE DIRECT ACTING REQUIRING NO
 MORE THAN ONE OPERATION.