2003-07-14 00:00:00 | | | *** ISSUED PERMIT*** | | -PLAN REVIEW HISTORY- | | | | PERMIT# 03051763 | | ADDRESS: 2345 CURLEY CUT | | CONT: SIERRA | | TELL # (561) 616-9686 | | | | THE ATTACHED COMMENTS ARE PART OF THE | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | *****BUILDING PROVISO****** | | | | 1)FL BLD CODE 104.2.1.2 | | ADDITIONAL INFORMATION REQUIRED, | | DISCREPANCY: ENERGY CALS VS FLOOR PLAN | | | | 2) STORM SHUTTERS | | A) KEY PLAN | | B) BOTTOM FASTENER CAULK-IN, THE VALUE | | TAKEN IS FOR CONCRETE, NOT CEMENT BLOCK! | | THIS FASTENER MAY NOT BE USED IN BLOCK, | | OR IF THIS IS USED IN FILLED CELL, THE | | CAULK-IN MUST BE IN 2500 PSI CONCRETE | | (FILLED CELL). OTHER ALTERNATIVE IS A | | DIFFERENT FASTENER FOR BLOCK. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|