2003-07-01 00:00:00 | ******CORRECTIONS******* |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)THE VALUE HAS BEEN ADJUSTED (SEE |
| ATTACHED); ADDITIONAL FEES OWED, $73.78. |
| |
| 2.)THE "NEW COVER PORCH" (NEW PLAN |
| VIEW AND EXIST PLAN VIEW) SHOULD BE |
| SHOWN AS AN EXISTING COVERED PORCH. |
| |
| 3.)SEPARATE PERMITS REQUIRED. |
| |
| 4.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 5.)THE SLIDING GLASS DOORS ARE NOT |
| LEGIBLE.THE WINDOW PRODUCT APPROVALS ARE |
| INCOMPLETE.SEE ATTACHED FOR INSTRUCTIONS |
| AS TO HOW TO OBTAIN DADE COUNTY PRODUCT |
| APPROVALS ONLINE. |
| |
| 6.)THE WINDOW & DOOR ANCHOR DETAIL |
| CONFLICTS WITH THE PRODUCT APPROVALS, |
| SEE ATTACHED. |
| |
| 7.)THE TYP WOOD FRAME DETAIL SHOWS A 2 |
| X6 WALL; THIS IS IN CONFLICT WITH OTHER |
| DETAILS (2X4 WALL FRAMING). |
| |
| 8.)THE PLAN REFERS TO "ENGINEER" IN |
| ITEM #4, GENERAL NOTES.EITHER REMOVE |
| THE NOTE OR PUT THE ENGINEER'S TITLE |
| BLOCK AND SEAL ON THE PLAN. |
| |
| 9.)THE NOTE "R19 INSULATION" SHOULD |
| NOT SAY "OWNER OPTION".THIS IS THE |
| MINIMUM INSULATION REQUIRED AS PER |
| ENERGY CALC. |
| |
| 10.) SHOW THE R5 INSULATION ON THE |
| MASONRY ADJACENT WALL, EX TYP SECTION, |
| AS PER THE ENERGY CALC. |
| |
| 11.) FIRESTOP REQUIRED, FBC705.3. |
| |
| 12.) HOW WILL YOU KEEP WATER FROM |
| INTRUDING AT THE BASE OF THE WALL? |