2004-02-05 00:00:00 | *****CORRECTIONS***** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 | | | | 1.)SEE OTHER PLAN REVIEWER'S COMMENTS | | IN REGARDS TO INFORMATION REQUIRED ON | | THE TITLE BLOCK. | | | | 2.)SHEET A3 DOES NOT AGREE WITH SHEET | | S8 IN REGARDS TO THE ROOF TOP UNITS. | | | | 3.)THE NEW WOOD BEAM ON SHEET A1 | | DATED 11/6/03 REFERS TO STRUCTURALS | | WHICH ARE NOT ON THE PLAN.PROVIDE A | | STRUCTURAL DETAIL. | | | | 4.)THE BRAILLE FLOOR DESIGNATION IS | | TO BE ON BOTH JAMBS AND TO COMPLY WITH | | FBC11-4.10.5. |
|