Date |
Text |
2003-07-26 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| FBC-2001 AMENDMENTS, CHAPTER |
| ONE, ADMIN. CODE |
| FLORIDA STATUTES. |
| |
| A) MOST COMMENTS FROM ORIGINAL REVIEW |
| HAVE NOT BEEN ADDRESSED. ORIGINAL NUMBER |
| SHALL BE SHOWN FOR CLAIRITY. |
| 1) ROUTE PLANS TO THE PALM BEACH COUNTY |
| HEALTH UNIT DIVISION OF ENVIRONMENTAL |
| HEALTH, 901 EVERNIA ST. W.P.B. FOR RE- |
| VIEW PRIOR TO RESUBMITTING TO THE CITY |
| FOR PLAN REVIEW. SEC 101.4.7 |
| 3) SHT A-9 SECTION 11-4.22.4 WHERE 6 OR |
| MORE STALLS ARE PROVIDED, IN ADDITION TO |
| THE STALL COMPLYING WITH 11-4.17.3, AT |
| LEAST ONE STALL 36" WIDE WITH AN OUTWARD |
| SWINGING, SELF-CLOSING DOOR AND PARALLEL |
| GRAB BARS COMPLYING WITH FIGURE 30(D) & |
| 11-4.26 SHALL BE PROVIDED. |
| 4) SHT P-1 MAIN HIP HOP BAR, NO SANT. |
| DRAIN LINE SHOWN FOR HAND SINK. ALSO NO |
| SANT. DRAIN LINE SHOWN FOR ICE MACHINES. |
| PLEASE CLAIRFY. SECTION 104.2.1 |
| 5) SHTS P-1 & P-3 CLEANOUT BY BAR #2 |
| SHALL CLEAN IN THE DIRECTION OF FLOW. |
| SEE RED LINE CORRECTIONS ON FLOOR PLAN & |
| SANITARY RISER DIAGRAM. SEC 708.3.3 |
| 6) SHT P-2 NO WATER SHOWN FOR THE ICE |
| MACHINES. PLEASE CLAIRFY. SEC 104.2.1 |
| 7) SHT P-2 GENERAL PLUMBING NOTES: |
| #11 CONDENSATE SHALL RUN SEPARATELY OUT |
| OF THE BLDG AND TIE INTO STORM, A CATCH |
| BASIN, OR A DRYWELL. UTILITY ORDINANCE |
| 90-125(5) |
| #12 AIR CHAMBERS ARE NOT APPROVED. DE- |
| LETE FROM REFERENCE. SEC 604.9 |
| 8) SHT P-4 ELECTRIC WATER HEATER DETAIL, |
| EMERGENCY PAN REQUIRED SEC 504.8. THERM- |
| AL EXPANSION CONTROL REQUIRED. SECTION |
| 607.3.2 |
| 9) SHT P-4 WATER RISER ISOMETRIC, AIR |
| CHAMBERS ARE NOT APPROVED. DELETE FROM |
| RISER DIAGRAM. WATER HAMMER ARRESTORS |
| SHALL BE LOCATED IN AN "EFFECTIVE RANGE" |
| NEAR THE FIXTURES NOT IN THE CEILING AT |
| THE TOP OF THE DROPS. PDI-WH 201 AND |
| MANUF. INSTALLATION INSTRUCTIONS. |
| 10) SHT P-4 WATER HEATER FOR PRIVATE |
| BATHROOM, T/P RELIEF VALVE SHALL DRAIN |
| TO A FLOOR SINK OR A HUB DRAIN. FUNNEL |
| DRAINS ARE NOT APPROVED. SEC'S 802.3 & |
| 802.3.2 |
| NEW COMMENTS....... |
| 11) ONLY ONE FULL SET OF PLANS HAS BEEN |
| SUBMITTED. OTHER ROLL OF PLANS HAVE ONLY |
| A2, A3, A4, A8, & A9 SHEETS. SUBMIT TWO |
| COMPLETE SETS OF PLANS. |
| 12) SEE ATTACHED SHEET CONCERNING |
| FLORIDA STATUTE 553.80(2)(B) DESIGN |
| PROFESSIONAL DOCUMENTS. NEXT REVIEW WILL |
| BE THE THIRD REVIEW. FIRST TWO HAVE THE |
| SAME COMMENTS. |
| ---------WHEN RESUBMITTING PLANS-------- |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |