Plan Review Notes
Plan Review Notes For Permit 03051657
Permit Number 03051657
Review Stop P
Sequence Number 3
Notes
Date Text
2003-07-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
 FLORIDA STATUTES.
  
 A) MOST COMMENTS FROM ORIGINAL REVIEW
 HAVE NOT BEEN ADDRESSED. ORIGINAL NUMBER
 SHALL BE SHOWN FOR CLAIRITY.
 1) ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH, 901 EVERNIA ST. W.P.B. FOR RE-
 VIEW PRIOR TO RESUBMITTING TO THE CITY
 FOR PLAN REVIEW. SEC 101.4.7
 3) SHT A-9 SECTION 11-4.22.4 WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION TO
 THE STALL COMPLYING WITH 11-4.17.3, AT
 LEAST ONE STALL 36" WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND PARALLEL
 GRAB BARS COMPLYING WITH FIGURE 30(D) &
 11-4.26 SHALL BE PROVIDED.
 4) SHT P-1 MAIN HIP HOP BAR, NO SANT.
 DRAIN LINE SHOWN FOR HAND SINK. ALSO NO
 SANT. DRAIN LINE SHOWN FOR ICE MACHINES.
 PLEASE CLAIRFY. SECTION 104.2.1
 5) SHTS P-1 & P-3 CLEANOUT BY BAR #2
 SHALL CLEAN IN THE DIRECTION OF FLOW.
 SEE RED LINE CORRECTIONS ON FLOOR PLAN &
 SANITARY RISER DIAGRAM. SEC 708.3.3
 6) SHT P-2 NO WATER SHOWN FOR THE ICE
 MACHINES. PLEASE CLAIRFY. SEC 104.2.1
 7) SHT P-2 GENERAL PLUMBING NOTES:
 #11 CONDENSATE SHALL RUN SEPARATELY OUT
 OF THE BLDG AND TIE INTO STORM, A CATCH
 BASIN, OR A DRYWELL. UTILITY ORDINANCE
 90-125(5)
 #12 AIR CHAMBERS ARE NOT APPROVED. DE-
 LETE FROM REFERENCE. SEC 604.9
 8) SHT P-4 ELECTRIC WATER HEATER DETAIL,
 EMERGENCY PAN REQUIRED SEC 504.8. THERM-
 AL EXPANSION CONTROL REQUIRED. SECTION
 607.3.2
 9) SHT P-4 WATER RISER ISOMETRIC, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE"
 NEAR THE FIXTURES NOT IN THE CEILING AT
 THE TOP OF THE DROPS. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 10) SHT P-4 WATER HEATER FOR PRIVATE
 BATHROOM, T/P RELIEF VALVE SHALL DRAIN
 TO A FLOOR SINK OR A HUB DRAIN. FUNNEL
 DRAINS ARE NOT APPROVED. SEC'S 802.3 &
 802.3.2
 NEW COMMENTS.......
 11) ONLY ONE FULL SET OF PLANS HAS BEEN
 SUBMITTED. OTHER ROLL OF PLANS HAVE ONLY
 A2, A3, A4, A8, & A9 SHEETS. SUBMIT TWO
 COMPLETE SETS OF PLANS.
 12) SEE ATTACHED SHEET CONCERNING
 FLORIDA STATUTE 553.80(2)(B) DESIGN
 PROFESSIONAL DOCUMENTS. NEXT REVIEW WILL
 BE THE THIRD REVIEW. FIRST TWO HAVE THE
 SAME COMMENTS.
 ---------WHEN RESUBMITTING PLANS--------
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]