Plan Review Notes For Permit 03051657 |
Permit Number |
03051657 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-07-24 00:00:00 | 1) STAIR LANDING SHALL BE AT LEAST | | FOUR FEET WIDE BY USING THE EXCEPTION | | IN THE LIFE SAFETY CODE 7.2.2.3.2 | | | | 2) WHAT PREVENTS THE EXIT DOORS LOCATED | | ON THE NORTH SIDE FROM BEING BLOCKED. | | SIGNS OF THE BACKS OF THIS DOORS | | STATING "EXIT DOOR, DO NOT BLOCK. | | | | 3) PROVIDE SURVEY TO CONFIRM EXIT | | DISCHARGE LOCATIONS. DOORS CANNOT | | OPEN ONTO PUBLIC RIGHT OF WAYS. | | | | 4) ITEM # 12 OF YOUR RESPONSE IS | | INCORRECT. THE NEW ELEVATOR IS A SHAFT | | AND SHALL BE MARKED AS ONE. | | | | 5) OCCUPANT LOAD SIGN IS REQUIRED TO | | BE POSTED AFTER CONFIRMATION WITH | | THE BUREAU OF FIRE PREVENTION. | | | | 6) PLANS INDICATE A NEW FIRE ALARM | | CONTROL PANEL. PLEASE INDICATE WHERE | | FIRE ALARM DEVICES CAN BE LOCATED. | | | | 7) PLEASE INDICATE WHERE INTERIOR | | FINISH CLASSIFICATION INFORMATION | | CAN BE LOCATED. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|