Plan Review Notes
Plan Review Notes For Permit 03051657
Permit Number 03051657
Review Stop E
Sequence Number 2
Notes
Date Text
2004-01-30 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 AS REQ'D UNDER FS 471.023 ON TITLE
 BLOCK. PER FAC 61G15-23.002
  
 2)NOTE: PLEASE CORRELATE AIC RATING
 SHOWN FOR MDP. RISER SHOWS A MIN OF
 40,000 AND MDP PANLE SHOWS @ 22,000??
 PLEASE CORRECT. 110.9
  
 3)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS AND PANEL SCHEDULES. EM LT AND EXT
 LTS DO NOT CORRELATE WITH PANEL SCHEDULE
 . ALL TO BE CIRCUITED PER 700.12E.
  
 4)NOTE: PLEASE CLARIFY REQ'D SIGN CIR-
 -CUIT PER 600.5
  
 5)NOTE: PLEASE SEE MISSING LICENSE #S
 FROM ARCH'S TITLE BLOCKS, ALSO REQ'D
 PER FS 481.219 AND FAC 61G1-16.004
 ARCH'S # AND FIRM LICENSE # REQ'D
 WEATHER OR NOT COMMENT IS MADE BY ANY
 OTHER REVIEWER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]