Plan Review Notes For Permit 03051657 |
Permit Number |
03051657 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-07-22 00:00:00 | SHEET A2 DATED 7/1103 SHOWS A 3' WIDE | | LANDING ON THE MAIN STAIRS IN THE | | DIRECTION OF TRAVEL.FBC 1007.4.2 | | REQUIRES A MINIMUM OF 4'.PLEASE | | REVISE AS NECESSARY. | | | | FBC 1007.5.7 REQUIRES HANDRAILS WITHIN | | 30" OF ALL PORTIONS OF THE STAIRS | | REQUIRED FOR EGRESS.PLEASE REVISE AS | | NECESSARY. | | | | THE STRUCTURAL SHEETS ARE THE SAME, | | CONSEQUENTLY SO ARE THE PREVIOUS | | COMMENTS.THE LIST PROVIDED ON | | 6/25/03 IS ATTACHED AGAIN. | | | | SHEET S1 DECLARES AN IMPORTANCE FACTOR | | OF 1.0.THIS BUILDING WILL HAVE >300 | | PEOPLE IN ONE ROOM SO WILL BE A | | CATEGORY III, TABLE 1-1, ASCE 7-98 AND | | REQUIRES AN | | IMPORTANCE FACTOR OF 1.15, SEE TABLE | | 6-1. | | | | THE PLANS MUST BE REVIEWED BY THE COUNTY | | FOR IMPACT FEES. AND THE PERMIT | | VALUATION ACCOUNTED FOR. |
|