Plan Review Notes
Plan Review Notes For Permit 03051657
Permit Number 03051657
Review Stop B
Sequence Number 2
Notes
Date Text
2003-07-22 00:00:00SHEET A2 DATED 7/1103 SHOWS A 3' WIDE
 LANDING ON THE MAIN STAIRS IN THE
 DIRECTION OF TRAVEL.FBC 1007.4.2
 REQUIRES A MINIMUM OF 4'.PLEASE
 REVISE AS NECESSARY.
  
 FBC 1007.5.7 REQUIRES HANDRAILS WITHIN
 30" OF ALL PORTIONS OF THE STAIRS
 REQUIRED FOR EGRESS.PLEASE REVISE AS
 NECESSARY.
  
 THE STRUCTURAL SHEETS ARE THE SAME,
 CONSEQUENTLY SO ARE THE PREVIOUS
 COMMENTS.THE LIST PROVIDED ON
 6/25/03 IS ATTACHED AGAIN.
  
 SHEET S1 DECLARES AN IMPORTANCE FACTOR
 OF 1.0.THIS BUILDING WILL HAVE >300
 PEOPLE IN ONE ROOM SO WILL BE A
 CATEGORY III, TABLE 1-1, ASCE 7-98 AND
 REQUIRES AN
 IMPORTANCE FACTOR OF 1.15, SEE TABLE
 6-1.
  
 THE PLANS MUST BE REVIEWED BY THE COUNTY
 FOR IMPACT FEES. AND THE PERMIT
 VALUATION ACCOUNTED FOR.