Plan Review Notes
Plan Review Notes For Permit 03051657
Permit Number 03051657
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 ADMIN. CODE, CHAPTER
 1, & AMENDMENTS.
  
 1) ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH, 901 EVERNIA ST W.P.B. FOR REVIEW
 PRIOR TO RESUBMITTING TO THE CITY FOR
 PLAN REVIEW. SEC 101.4.7
 2) SHT A-3 BATHROOM #310, 11-4.1.3(11).
 OTHER TOILET ROOM PROVIDED FOR THE USE
 OF OCCUPANTS OF SPECIFIC SPACES (I.E. A
 PRIVATE TOILET FOR THE OCCUPANT OF A
 PRIVATE OFFICE) SHALL BE ADAPTABLE. SUB-
 MIT DETAIL, SHOWING TURNING CIRCLE, AND
 BACKING GRAB BARS FOR TOILET AND SHOWER.
 SHOW CONTROL AREA FOR SHOWER AND CURB
 PER SECTIONS 11-4.16.4, 11-4.21.4, 11-4.
 21.5, AND 11-4.21.7.
 3) SHT A-9 SECTION 11-4.22.4 WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION TO
 THE STALL COMPLYING TO 11-4.17.3, AT
 LEAST ONE STALL 36" WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND PARALLEL
 GRAB BARS COMPLYING WITH FIGURE 30(D) &
 11-4.26 SHALL BE PROVIDED.
 4) SHT P-1 MAIN HIP HOP BAR, NO SANT.
 DRAIN LINE SHOWN FOR HAND SINK. ALSO NO
 SANT. DRAIN LINE SHOWN FOR ICE MACHINES.
 PLEASE CLAIRFY. SEC 104.2.1
 5) SHTS P-1 & P-3 CLEANOUT BY BAR #2
 SHALL CLEAN IN THE DIRECTION OF FLOW.
 SEE REDLINE CORRECTIONS ON FLOOR PLAN &
 SANITARY RISER DIAGRAM. SEC 708.3.3
 6) SHT P-2 NO WATER SHOWN FOR THE ICE
 MACHINES. PLEASE CLAIRFY. SEC 104.2.1
 7) SHT P-2 GENERAL PLUMBING NOTES:
 #11 CONDENSATE SHALL RUN SEPARATELY OUT
 OF THE BLDG AND TIE INTO STORM,A CATCH
 BASIN, OR A DRYWELL. UTILITY ORDINANCE
 90-125(5)
 #12 AIR CHAMBERS ARE NOT APPROVED. DE-
 LETE FROM REFERENCE. SEC 604.9
 8) SHT P-4 ELECTRIC WATER HEATER DETAIL,
 EMERGENCY PAN REQUIRED SEC 504.8. THERM-
 AL EXPANSION CONTROL REQUIRED. SECTION
 607.3.2.
 9) SHT P-4 WATER RISER ISOMETRIC, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE"
 NEAR THE FIXTURE NOT IN THE CEILING AT
 THE TOP OF THE DROPS. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 10) SHT P-4 WATER HEATER FOR PRIVATE
 BATHROOM, T/P RELIEF VALVE SHALL DRAIN
 TO A FLOOR SINK OR A HUB DRAIN. FUNNEL
 DRAINS ARE NOT APPROVED. SEC'S 802.3 &
 802.3.2.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692