2003-06-14 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| FBC-2001 ADMIN. CODE, CHAPTER |
| 1, & AMENDMENTS. |
| |
| 1) ROUTE PLANS TO THE PALM BEACH COUNTY |
| HEALTH UNIT DIVISION OF ENVIRONMENTAL |
| HEALTH, 901 EVERNIA ST W.P.B. FOR REVIEW |
| PRIOR TO RESUBMITTING TO THE CITY FOR |
| PLAN REVIEW. SEC 101.4.7 |
| 2) SHT A-3 BATHROOM #310, 11-4.1.3(11). |
| OTHER TOILET ROOM PROVIDED FOR THE USE |
| OF OCCUPANTS OF SPECIFIC SPACES (I.E. A |
| PRIVATE TOILET FOR THE OCCUPANT OF A |
| PRIVATE OFFICE) SHALL BE ADAPTABLE. SUB- |
| MIT DETAIL, SHOWING TURNING CIRCLE, AND |
| BACKING GRAB BARS FOR TOILET AND SHOWER. |
| SHOW CONTROL AREA FOR SHOWER AND CURB |
| PER SECTIONS 11-4.16.4, 11-4.21.4, 11-4. |
| 21.5, AND 11-4.21.7. |
| 3) SHT A-9 SECTION 11-4.22.4 WHERE 6 OR |
| MORE STALLS ARE PROVIDED, IN ADDITION TO |
| THE STALL COMPLYING TO 11-4.17.3, AT |
| LEAST ONE STALL 36" WIDE WITH AN OUTWARD |
| SWINGING, SELF-CLOSING DOOR AND PARALLEL |
| GRAB BARS COMPLYING WITH FIGURE 30(D) & |
| 11-4.26 SHALL BE PROVIDED. |
| 4) SHT P-1 MAIN HIP HOP BAR, NO SANT. |
| DRAIN LINE SHOWN FOR HAND SINK. ALSO NO |
| SANT. DRAIN LINE SHOWN FOR ICE MACHINES. |
| PLEASE CLAIRFY. SEC 104.2.1 |
| 5) SHTS P-1 & P-3 CLEANOUT BY BAR #2 |
| SHALL CLEAN IN THE DIRECTION OF FLOW. |
| SEE REDLINE CORRECTIONS ON FLOOR PLAN & |
| SANITARY RISER DIAGRAM. SEC 708.3.3 |
| 6) SHT P-2 NO WATER SHOWN FOR THE ICE |
| MACHINES. PLEASE CLAIRFY. SEC 104.2.1 |
| 7) SHT P-2 GENERAL PLUMBING NOTES: |
| #11 CONDENSATE SHALL RUN SEPARATELY OUT |
| OF THE BLDG AND TIE INTO STORM,A CATCH |
| BASIN, OR A DRYWELL. UTILITY ORDINANCE |
| 90-125(5) |
| #12 AIR CHAMBERS ARE NOT APPROVED. DE- |
| LETE FROM REFERENCE. SEC 604.9 |
| 8) SHT P-4 ELECTRIC WATER HEATER DETAIL, |
| EMERGENCY PAN REQUIRED SEC 504.8. THERM- |
| AL EXPANSION CONTROL REQUIRED. SECTION |
| 607.3.2. |
| 9) SHT P-4 WATER RISER ISOMETRIC, AIR |
| CHAMBERS ARE NOT APPROVED. DELETE FROM |
| RISER DIAGRAM. WATER HAMMER ARRESTORS |
| SHALL BE LOCATED IN AN "EFFECTIVE RANGE" |
| NEAR THE FIXTURE NOT IN THE CEILING AT |
| THE TOP OF THE DROPS. PDI-WH 201 AND |
| MANUF. INSTALLATION INSTRUCTIONS. |
| 10) SHT P-4 WATER HEATER FOR PRIVATE |
| BATHROOM, T/P RELIEF VALVE SHALL DRAIN |
| TO A FLOOR SINK OR A HUB DRAIN. FUNNEL |
| DRAINS ARE NOT APPROVED. SEC'S 802.3 & |
| 802.3.2. |
| |
| REVIEW BY KEN STEVENS |