Plan Review Notes
Plan Review Notes For Permit 03051635
Permit Number 03051635
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-10 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)ADDITIONAL FEES REQUIRED.
  
 3.)WINDOW HEAD & SILL, WINDOW JAMB
 DETAILS; BUCK MUST COMPLY WITH FBC
 1707.4.4.2.THE DETAILS ALSO CONFLICT
 WITH THE PRODUCT APPROVALS.
  
 4.)FBC 3401.7.1, IN REGARDS TO
 ADDITIONS OF OVER 25%, SHOW BEDROOM
 EMERGENCY EGRESS AND SMOKE DETECTORS
 IN EXISTING BEDROOMS.
  
 5.)ENERGY CALCS SPECIFY R5 INSULATION,
 WALL SECTION (A4) SHOWS R3.
  
 6.)TRUSS ANCHORS UPLIFT EXCEED THE
 MAXIMUM UPLIFT SPECIFIED IN THE
 CATALOG.SEE USP 2003 CATALOG, AND ALSO
 READ PP 6-7 REGARDING STRESS INCREASES
 FOR STEEL.
  
 7.)FIRESTOP REQUIRED, FBC 705.3.
  
 8.)SHOW THE 4" ABOVE GRADE, 12" MIN.
 BELOW GRADE FOR THE FOOTER (WALL SECTION
 A4).
  
 9.)SOFFIT VENTS REQUIRED, SPECIFY
 SIZE AND SPACING TO COMPLY WITH FBC
 2309.7.
  
 10.)1 1/2" WATERSTOP REQUIRED, CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FBC,
 2111.1.9.
  
 11.)PROVIDE DESIGN INFORMATION ON THE
 PLAN FBC 1606.1.7.