Plan Review Notes For Permit 03051635 |
Permit Number |
03051635 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-10 00:00:00 | ******CORRECTIONS******* | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)SEPARATE PERMITS REQUIRED. | | | | 2.)ADDITIONAL FEES REQUIRED. | | | | 3.)WINDOW HEAD & SILL, WINDOW JAMB | | DETAILS; BUCK MUST COMPLY WITH FBC | | 1707.4.4.2.THE DETAILS ALSO CONFLICT | | WITH THE PRODUCT APPROVALS. | | | | 4.)FBC 3401.7.1, IN REGARDS TO | | ADDITIONS OF OVER 25%, SHOW BEDROOM | | EMERGENCY EGRESS AND SMOKE DETECTORS | | IN EXISTING BEDROOMS. | | | | 5.)ENERGY CALCS SPECIFY R5 INSULATION, | | WALL SECTION (A4) SHOWS R3. | | | | 6.)TRUSS ANCHORS UPLIFT EXCEED THE | | MAXIMUM UPLIFT SPECIFIED IN THE | | CATALOG.SEE USP 2003 CATALOG, AND ALSO | | READ PP 6-7 REGARDING STRESS INCREASES | | FOR STEEL. | | | | 7.)FIRESTOP REQUIRED, FBC 705.3. | | | | 8.)SHOW THE 4" ABOVE GRADE, 12" MIN. | | BELOW GRADE FOR THE FOOTER (WALL SECTION | | A4). | | | | 9.)SOFFIT VENTS REQUIRED, SPECIFY | | SIZE AND SPACING TO COMPLY WITH FBC | | 2309.7. | | | | 10.)1 1/2" WATERSTOP REQUIRED, CITY OF | | WEST PALM BEACH AMENDMENTS TO THE FBC, | | 2111.1.9. | | | | 11.)PROVIDE DESIGN INFORMATION ON THE | | PLAN FBC 1606.1.7. |
|