Plan Review Notes For Permit 03051572 |
Permit Number |
03051572 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-08-08 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE SEE NOTES FROM LAST REVIEW,NO | | COMMENTS WERE ADDRESSED.(ATTACHED). | | | | PLEASE NOTE THAT ALL PLANS | | THAT ARE SIGNED AND SEALED BY ARCH/ OR | | ENGINEER ARE REQ`D PER 61G15-23.002 FOR | | ENGINEER AND 61G1-16.004 FOR ARCH. | | SHALL HAVE A TITLE BLOCK. | | | | THIS REVISION REMOVED THE REQUIRED | | RECEPTACLE FROM THE COUNTERTOP,IT MUST | | BE ADDED BACK TO CONFORM WITH | | 210.52(C)(1). | | | | THE GARAGE MUST COMPLY WITH 210.52(G) & | | 210.8. | | | | THERE MUST BE A RECEPTACLE IN THE | | BATHROOM PER 210.52(D). | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|