Plan Review Notes
Plan Review Notes For Permit 03051572
Permit Number 03051572
Review Stop E
Sequence Number 2
Notes
Date Text
2003-07-01 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 THE PLANS AND RESUBMIT FOR REVIEW PRIOR
 TO CALLING ANY ELECTRICAL INSPECTIONS.
  
 1} INDICATE CONDUIT AND WIRE TYPE AND
 SIZE FEEDING THE GARAGE.
  
 2} SHOW OCP ON MAIN PANEL SCHEDULE FOR
 GARAGE FEED.
  
 3} INDICATE DISCONNECTING MEANS PER 225.
 32 AND GROUNDING PER 250.32,FOR GARAGE
 FEED.
  
 4} THE RECEPTACLE ON THE COUNTER MUST
 COMPLY WITH 210.8(A)(7).GFI.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.LISTED WITH #14
 ON SCHEDULE.
  
 6} NOTE THAT THE HEAT LOAD IS LARGER
 THAN THE A/C LOAD AND MUST USED IN THE
 LOAD CALCULATION. PLEASE RECALCULATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718