Plan Review Notes For Permit 03051572 |
Permit Number |
03051572 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-07-01 00:00:00 | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE NECESSARY CHANGES TO | | THE PLANS AND RESUBMIT FOR REVIEW PRIOR | | TO CALLING ANY ELECTRICAL INSPECTIONS. | | | | 1} INDICATE CONDUIT AND WIRE TYPE AND | | SIZE FEEDING THE GARAGE. | | | | 2} SHOW OCP ON MAIN PANEL SCHEDULE FOR | | GARAGE FEED. | | | | 3} INDICATE DISCONNECTING MEANS PER 225. | | 32 AND GROUNDING PER 250.32,FOR GARAGE | | FEED. | | | | 4} THE RECEPTACLE ON THE COUNTER MUST | | COMPLY WITH 210.8(A)(7).GFI. | | | | 5} PLEASE LIST THE REQ'D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG.LISTED WITH #14 | | ON SCHEDULE. | | | | 6} NOTE THAT THE HEAT LOAD IS LARGER | | THAN THE A/C LOAD AND MUST USED IN THE | | LOAD CALCULATION. PLEASE RECALCULATE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|