2003-06-17 00:00:00 | BUILDING DENIED |
| |
| 1) A NEW NOTICE OF COMMENCEMENT WILL BE |
| REQUIRED TO BE RECORDED AND SUBMITTED |
| FOR THIS PERMIT. FLORIDA STATUTE 713.13 |
| REQUIRES THE WORK ON THE PROJECT TO |
| START WITHIN 90 DAYS OF RECORDING. |
| |
| 2) THE POSITIVE AND NEGATIVE PRESSURES |
| FOR THE DOOR TO THE GUEST COTTAGE THAT |
| WERE ADDED (DRAWN IN) ARE REQUIRED TO |
| BE INITIALED AND DATED. |
| |
| 3) THE PRODUCT APPROVAL FOR THE OVERHEAD |
| GARAGE DOOR DOES NOT HAVE DESIGN |
| PRESSURES CAPABLE OF WITHSTANDING THE |
| PRESSURES INDICATED ON THE PLAN. |
| |
| 4) THE PRODUCT APPROVAL SUBMITTED FOR |
| THE EXTERIOR DOORS IS FOR GLAZED FRENCH |
| DOORS, WHICH REQUIRE IMPACT PROTECTION. |
| SUBMIT A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. INDICATE |
| THE SPECIFIC TYPES OF ANCHORS THAT WILL |
| BE USED, SPACING ETC. INDICATE THE |
| LENGTH AND EMBED DEPTH OF THE 1/2" LAG |
| SCREWS SPECIFIED IN THE SHUTTER MOUNTING |
| DETAIL ON SHEET 1 OF THE PLANS. THE |
| ANCHOR SCHEDULE ON SHEET 6 OF THE STORM |
| PANEL PRODUCT APPROVAL DRAWINGS REQUIRES |
| 1/4" DIAMETER X MIN. 3" LONG LAG SCREW |
| WITH MIN. 2" EMBEDMENT. |
| |
| 5) CLARIFY WHY THE PROJECT DESCRIPTION |
| ON THE PERMIT APPLICATION WAS CHANGED |
| FROM GUEST COTTAGE TO POOL CABANA. THE |
| PLANS ARE FOR A GUEST COTTAGE. |
| |