2003-05-30 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - EXTERIOR WINDOWS |
| - EXTERIOR DOORS |
| - OVERHEAD GARAGE DOOR |
| |
| 3) THE FBC 1606.1.4 REQUIRES GLAZED |
| OPENINGS IN WINDBOURNE DEBRIS REGIONS TO |
| BE IMPACT RESISTANT OR PROTECTED WITH |
| IMPACT RESISTANT COVERINGS. |
| PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. |
| |
| 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 5) SPECIFY THE INSULATION FOR THE WALLS |
| AND ATTIC OF THE HABITABLE SPACE. FBC |
| CHAPTER 13 REQUIRES THE COMPONENTS BEING |
| REPLACED OR RETROFITTED TO COMPLY WITH |
| ENERGY CODE. |
| |
| 6) OPENINGS FROM A GARAGE DIRECTLY INTO |
| A ROOM USED FOR SLEEPING PURPOSES IS NOT |
| PERMITED PER FBC 411.2.8. |
| |
| 7) INDICATE THE POSITIVE AND NEGATIVE |
| DESIGN WIND PRESSURES FOR THE NEW DOOR |
| THAT WAS DRAWN IN. |
| |
| 8) ITEMS THAT WERE ADDED (DRAWN IN) TO |
| THE PLANS ARE REQUIRED TO BY INITIALED |
| AND DATED BY THE DESIGNER OF RECORD. |
| |
| 9) INDICATE ON THE PLAN THAT ADEQUATE |
| SUBSTRATE WILL BE PROVIDED FOR THE |
| ATTACHMENT OF THE HURRICANE PANELS. |
| |
| 10) REVIEW PLANS FOR SHEARWALL |
| COMPLIANCE PER FBC 2313. SPECIFY THE |
| NAIL SIZE AND SPACING FOR SHEAR WALL |
| PANELS PER FBC 2310.4. |
| |
| 11) IF WIRE MESH IS USED IN THE SLAB IT |
| IS REQUIRED TO BE SUPPORTED ON APPROVED |
| MATERIAL AT A MAXIMUM OF THREE FEET O.C. |
| PER FBC 1909.3. |
| |
| 12) THE NAIL SPACING FOR THE ROOF |
| SHEATHING HAS 6" THROUGHOUT IN ONE NOTE |
| AND 4"EDGES & 6" IN THE FIELD IN ANOTHER |
| PLEASE CORRECT. |
| |
| 13) SPECIFY THAT A 3"X3" WASHER IS |
| REQUIRED ON THE 1/2" ANCHOR BOLTS. |
| |
| 14) SPECIFY THE CONNECTOR THAT WILL BE |
| USED TO ATTACH THE BOTTOM PLATE TO THE |
| STUDS IN ORDER TO CREATE A CONTINOUS |
| LOAD PATH FROM THE ROOF TO FOUNDATION |
| PER FBC 1606.1.3. |
| |
| 15) THE UPLIFT VALUE IN THE TRUSS ANCHOR |
| SCHEDULE FOR THE (2) HTS-20 CONNECTORS |
| IS INCORRECT. THE VALUE SHOULD BE 2900# |
| (1450# EACH STRAP) PER 2003 SIMPSON |
| CATALOG. |
| |
| 16) NOTES UNDER WOOD FRAME CONSTRUCTION |
| ON SHEET 1 SPECIFIES 8D COMMON OR HOT |
| DIPPED GAL. NAILS AND NOTE ON SHEET 8 |
| CALLS FOR 8D RING SHANK NAILS FOR ROOF |
| SHEATHING ATTACHMENT. PLEASE CLARIFY. |
| |
| 17) PLEASE CLARIFY IF THE 3" SCREEN VENT |
| AT THE SOFFIT IS CONTINOUS. |
| |
| 18) SHEETS 2 THROUGH 7 OF THE DRAWINGS |
| ARE MISSING. PLEASE CLARIFY. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |