Plan Review Notes
Plan Review Notes For Permit 03051400
Permit Number 03051400
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-03 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE RESUBMIT THE FOLLOWING PRIOR TO
 ROUGH ELECTRICAL INSPECTION.
  
 1} THE PLANS SHOW 2 AIR HANDLERS AND
 ONLY ONE WAS INCLUDED IN THE ELECTRICAL
 LOAD CALCULATION.
  
 2} THE GARBAGE DISPOSAL ON THE PANEL
 SCHEDULE SHOWS NO CIRCUIT NUMBER AND NO
 LOAD.
  
 3} THE GARAGE RECEPTACLES MUST COMPLY WI
 TH 210-8(A)(2).
  
 PLEASE REVISE THE LOAD TO INDICATE
 ACTUAL CONDITIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718