Plan Review Notes
Plan Review Notes For Permit 03051398
Permit Number 03051398
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-16 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-STORM SHUTTERS: ANCHORS TO BE 12"O.C
 MAXIMUM (NOT 12.5") IF EDGE DISTANCE
 IS 2". SEE ENGINEERED DRAWINGS.
 2-REVISE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T
 ALLOW THE STEEL STRESSS INCREASE TO
 BE USED.