2003-06-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED ALTERATIONS MAY REQUIRE
 PAYMENT OF IMPACT FEES.THE PROPOSALS
 SHOULD BE ASSESSED BY PALM BEACH COUNTY,
 THE PLANS STAMPED BY THEM AND A COPY OF
 THE RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT BEFORE A BUILDING PERMIT CAN
 BE ISSUED.
  
 3) FBC 1606.1.7SHEET S2, STRUCTURAL
 NOTES, CODES AND STANDARDS #1.IN
 ADDITION TO THE INFORMATION PROVIDED,
 THE PLANS SHALL ALSO STATE THE DESIGN
 WIND PRESSURES FOR SPECIFICATION OF THE
 ROOF COVERINGS AND NEW FRENCH DOOR.
  
 4) ROOF COVERING.THE SUBMITTAL OF A
 PRODUCT APPROVAL IS NOTED.THE PLANS
 DO NOT STATE WHAT TYPE OF ROOF COVERING
 IS TO BE PROVIDED.AMEND THE PLANS TO
 SPECIFY THE TYPE OF ROOF SYSTEM/MATERIAL
 OVER THE NEW FRONT PORCH AND THE
 EXISTING REAR PORCH (FOLLOWING REMOVAL
 THE SECOND FLOOR 'BONUS ROOM')
  
 5) FBC 1005.4.1REMOVAL OF EXISTING
 EXTERIOR DOOR.ANNOTATE THE BEDROOMS ON
 THE PLAN.IS THE EXTERIOR DOOR BEING
 REMOVED FROM A BEDROOM, AND IF SO DO THE
 REMAINING WINDOWS COMPLY WITH THE
 REQUIREMENTS FOR EMERGENCY EGRESS
 OPENINGS?ANNOTATE THE PLANS
 ACCORDINGLY.
  
 6) FBC 2304.2.5SHEET S3, SOUTH
 ELEVATION, PATCHING OF WOOD SIDING AFTER
 REMOVAL OF THE EXISTING EXTERIOR DOOR.
 THE WOOD SIDING SHALL BE AT LEAST 6"
 CLEAR OF THE GROUND.
  
 7) THE PLANS SHALL STATE THE DIMENSIONS
 (AS "NOT TO EXCEED.." IF NECESSARY) FOR
 THE NEW FRONT PORCH.WHAT IS THE
 SPACING OF THE COLUMNS?FROM THE
 SIMPSON CATALOGUE, THE ABA44 COLUMN BASE
 ANCHORS MAY HAVE INSUFFICIENT UPLIFT
 CAPACITY.CHECK AFTER ESTABLISHING THE
 PORCH DIMENSIONS.
  
 8) FBC 1804.1.3 AND FBC 1606.1.3
 SHEETS S2, PORCH SECTION.THE DOWELLED
 EXTENSION TO THE EXISTING PORCH SLAB IS
 SHOWN TO BE SUPPORTING THE NEW PORCH
 COLUMNS.THE COLUMNS SHALL BE
 ANCHORED TO A FOUNDATION CAPABLE OF
 RESISTING WIND-INDUCED UPLIFT.ALSO THE
 BOTTOM OF FOUNDATIONS SHALL EXTEND NO
 LESS THAN 12" BELOW FINISHED GRADE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS